Installer Setting - Installer Setting Code Table

Installer Setting Code Table
No.
Function
Ceiling Height
1
Selection
2
Group Control
Ceiling Height Selection
Indoor unit connected to wired remote controller operate as wired remote controller setting.
Cooling performance is enhanced with relation to ceiling height. The highest cooling
performance and efficiency are provide at super high. (Some noise may be generated
according to the level height setting.)
Group Control
This function is only for group control. Please don't set this function in case of non-group
control.
After setting Group Control of the product, turn off the power then turn it back on after 1
minute.

SELF-DIAGNOSIS FUNCTION

Error
Code
01
Indoor Air Sensor (Open/Short)
02
Indoor In Pipe Sensor (Open/Short)
05
Communication Failure (Indoor Unit ↔ Outdoor Unit)
06
Indoor Out Pipe Sensor (Open/Short)
09
Indoor EEPROM Error
10
Indoor Fan Lock Error
12
Indoor Middle Pipe Sensor (Open/Short)
Function Code
1 : Standard
2 : Low
1
3 : High
4 : Super High
0 : Set to Master
2
1 : Set to Slave
2 : Check Master/Slave
Description
Setting Value
Error Indication
Indoor Unit
LED2
-
1 Time
-
2 Times
-
5 Times
-
6 Times
-
9 Times
1 Time
1 Time
2 Times
Remote Controller LCD
Outdoor Unit
LED1
Red
Green
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-