Technical Specifications - Samsung AC MXAD H Series Installation Manual

Table of Contents

Advertisement

Appendix
No. Error Code
Cooling operation restricted at outdoor temperature
22
E441
below Tcool_low value (default:0°C)
23
E458
Fan speed error
24
E461
Error due to operation failure of inverter compressor
25
E462
System stop due to full current control
26
E463
Over current trip / PFC over current error
27
E464
IPM Over Current(O.C)
28
E465
Comp. Over load error
29
E466
DC-Link voltage under/over error
Error due to abnormal rotation of the compressor or
30
E467
unconnected wire of compressor
31
E468
Error on current sensor (Short or Open)
32
E469
Error on DC-Link voltage sensor (Short or Open)
33
E470
Outdoor unit EEPROM Read/Write error (Option)
34
E471
Outdoor unit EEPROM Read/Write error (H/W)
Error on IPM Heat Sink sensor of inverter 1 (Short or
35
E474
Open)
36
E475
Error on inverter fan 2
37
E483
Overvoltage of H/W detect DC link
38
E484
PFC Overload (Over current) Error
39
E485
Error on input current sensor of inverter 1 (Short or Open) Check Outdoor EEPROM PBA
40
E488
Inverter input voltage sensor error
41
E500
IPM over heat error on inverter 1
42
E508
Smart install is not installed
43
E554
Gas leak detected
Error due to mismatching capacity of indoor and outdoor
44
E556
unit
45
E557
DPM remote controller option error
46
E590
Inverter EEPROM Checksum error

Technical specifications

Model
AC090MXADKH
AC090MXADNH
AC100MXADKH
AC100MXADNH
AC120MXADKH
AC120MXADNH
AC120MXASEH
AC140MXADKH
AC140MXADNH
32
English
Meaning
Net weight
72.0 kg
72.0 kg
72.0 kg
72.0 kg
77.0 kg
77.0 kg
77.0 kg
87.0 kg
87.0 kg
Remarks
1. Check the range of temperature limited for cooling
operation
2. Check the outdoor temperature sensor
FAN1 ERROR
-
-
Check OLP sensor
1. Check if the service valve is open
2. Check the state of refrigerant
3. Check if connecting wire and the pipe are OK
4. Check the compressor
-
Check AC Power and DC Link Voltage
Check Comp wire
Check Outdoor Inverter PBA.
-
Check Outdoor EEPROM Data
Check Outdoor EEPROM PBA
Check Outdoor Inverter PBA.
FAN2 ERROR
Check AC Power
Check Outdoor Inverter PBA.
Check Outdoor Inverter PBA
Check Outdoor Inverter PBA.
-
Check the refrigerant
Check the indoor and outdoor unit capacity
Check the indoor option code
-
Net dimension (W × D × H)
940 mm × 330 mm × 998 mm
940 mm × 330 mm × 998 mm
940 mm × 330 mm × 998 mm
940 mm × 330 mm × 998 mm
940 mm × 330 mm × 998 mm
940 mm × 330 mm × 998 mm
940 mm × 330 mm × 998 mm
940 mm × 330 mm × 1210 mm
940 mm × 330 mm × 1210 mm