TROUBLESHOOTING

8-1. TROUBLESHOOTING
<Check code displayed by self-diagnosis and actions to be taken for service (summary)>
Present and past check codes are logged, and they can be displayed on the wired remote controller and control board of out-
door unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summa-
rized in the table below. Check the contents below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
8-2. CHECK POINT UNDER TEST RUN
Before test run
• After installation of outdoor units, piping work and electric wiring work, re-check that there is no water leakage, loosened
connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block (L, N) on the outdoor unit by 500 V Megger
and check that it is 1.0 M or over.
• Turn on power supply 12 hours before test run in order to protect compressor.
• Make sure to read operation manual before test run. (Especially items to secure safety.)
OCH562D
Check code
Judge the problem and take a corrective action according
to "8-3. SELF-DIAGNOSIS ACTION TABLE".
Displayed
Conduct troubleshooting and ascertain the cause of the
trouble.
Not displayed
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise, etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
Logged
trouble occurred, matters related to wiring, etc.
2Reset check code logs and restart the unit after finishing
service.
3There is no abnormality in electrical component,
controller board, etc.
1Re-check the abnormal symptom.
2Conduct troubleshooting and ascertain the cause of the
trouble.
3Continue to operate unit for the time being if the cause
is not ascertained.
Not logged
4There is no abnormality concerning of parts such as
electrical component, controller board, etc.
16
Actions to be taken for service (summary)