If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.
Main power source
Air
Conditioner
Connect the cable to the indoor unit
1. Connect the wires to the terminals on the control
board individually according to the outdoor unit con-
nection.
• Ensure that the color of the wires of outdoor unit and the
terminal No. are the same as those of indoor unit respec-
tively.
(Refer to Wiring diagram on page11.)
WARNING
• Be sure to refer to the wiring diagram label inside the
cover control and carry out the correct field wiring.
Wrong wiring can cause the unit to misoperate to result
in a fire hazard.
• Check local electrical codes and any specified wiring
instructions or limitations.
2. Attach the Grille onto the cabinet.
• Grasp lower the left and right side of the Grille and
engage four tabs on the top inside edge of the chassis.
• Press the Grille toward the chassis until it will be back into
place.
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
CAUTION
CAUTION
Circuit Breaker
Model
Use a circuit
breaker or time
delay fuse.
- 30 -
Power source Fuse or breaker
18K
1ø,230/208V
24K
1ø,230/208V
Connecting cable
LGE Internal Use Only
Capacity
15A
20A