8 Operation Details

8.1.

Indoor Fan Speed Control

• • • • Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
• • • • Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button at the remote
control.
8.2.

Cooling Mode Operation

Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
• • • • If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• • • • When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
7 minutes Time Save Control
• • • • The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
Anti-Freezing Control
• • • • If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
• • • • Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.