6. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as follows.
Intake Air temp.
Setting temp.+3°C
(Compressor OFF)
Setting temp.
(Compressor ON)
INDOOR FAN
COMPRESSOR
A point; While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed, when
it becomes lower than 40˚C fan stops.
B point; When the indoor Heat-Exchanger temperature is higher than 42°C, fan operates at selected fan
speed, when it becomes lower than 39°C, the fan operates at low speed.
7. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature reaches to 25°C.
• If the evaporator piping temperature drops below 22°C, indoor fan stops again.
• The operation diagram is as follows.
minimum 3min
minimum
1min
(Hot Start)
Selected
Low
OFF
Fan Speed
ON
PIPING
TEMPERATURE
25°C
22°C
INDOOR FAN
COMPRESSOR
A
10sec.
Low
OFF
OFF
1min
OFF
LOW
ON
–17–
B
minimum
minimum
10sec.
1min.
Selecting fan
Low
Low
speed
ON
Selected
fan speed
A
OFF
OFF