Specifications Of Standard Wiring Components; To Connect The Electrical Wiring To The Outdoor Unit - Daikin 3MXM40A2V1B Installation Manual

Hide thumbs Also See for 3MXM40A2V1B:
Table of Contents

Advertisement

WARNING
Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.
WARNING
▪ Do NOT use locally purchased electrical parts inside
the product.
▪ Do NOT branch the power supply for the drain pump,
etc. from the terminal block. This could result in
electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes
without thermal insulation as such pipes will be very hot.
DANGER: RISK OF ELECTROCUTION
All electrical parts (including thermistors) are powered by
the power supply. Do NOT touch them with bare hands.
DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10  minutes,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing. The
voltage MUST be less than 50 V DC before you can touch
electrical components. For the location of the terminals,
see the wiring diagram.
a
AL2 AL1
b
c
S40
FU2
DC(-)
DC
d
DC
AC
a
AL1, AL2 - solenoid valve lead wire connector*
b
S20~24 - electronic expansion valve coil lead wire
connector (room A, B, C, D, E)*
c
S40 – thermal overload relay lead wire and high pressure
switch connector*
d
Multimeter (DC voltage range)
e
S90~93 – thermistor lead wire connector
f
S70 - fan motor lead wire connector
g
S80 - 4-way valve lead wire connector
h
Compressor lead wire connector
*May differ depending on the model.
7.1
Specifications of standard wiring
components
Component
Power supply
Voltage
cable
Phase
Frequency
Wire type
Interconnection cable
(indoor↔outdoor)
2MXM-A, 3MXM-A, 4MXM-A, 5MXM-A
R32 Split series
3P600450-6M – 2021.12
S92
e
S93
f
g
S80
h
220~240 V
1~
50 Hz
See table below (A)
2
4-core cable 1.5 mm
or
2
2.5 mm
and applicable for
220~240 V
H05RN-F (60245 IEC 57)
Component
Recommended circuit breaker
Residual current device
Model
3MXM40
3- core cable 2.5 mm
2MXM68,
H05RN-F (60245 IEC 57)
3MXM52,
H07RN-F (60245 IEC 66)
3MXM68,
4MXM68
3- core cable 4.0 mm
H07RN-F (60245 IEC 66)
4MXM80
3- core cable 4.0 mm
5MXM90
H07RN-F (60245 IEC 66)
Electrical equipment must comply with EN/IEC 61000-3-12, the
European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and ≤75 A per phase.
7.2
To connect the electrical wiring to
the outdoor unit
1 Remove the switch box cover (1 screw).
2 Connect the wires between the indoor and outdoor units so that
the terminal numbers match. Make sure to match the symbols
for piping and wiring.
3 Make sure to connect correct wiring to correct room.
a-A
a-B
a-C
a-D
a-E
e-A
a
Terminal for room (A, B, C, D, E)*
b
Circuit breaker
c
Residual current device
d
Power supply wire
e
Interconnection wire for room (A, B, C, D, E)*
*May differ depending on the model.
4 Tighten the terminal screws securely using a Philips
screwdriver.
5 Check that the wires do not disconnect by pulling them lightly.
6 Firmly secure the wire retainer to avoid external stress on wire
terminations.
7 Pass the wiring through the cutout on the bottom of the
protection plate.
7 Electrical installation
See table below (B)
MUST comply with
applicable legislation
A
B
2
16 A
20 A
2
2
25 A
32 A
b
c
d
e-D
e-C
e-B
e-E
Installation manual
15