Fault messages
(cont.)
Displayed fault
System characteristics
code
F.386
Burner in a fault state
F.387
Burner in a fault state
F.388
Burner in a fault state
F.395
Burner in a fault state
F.396
Burner in a fault state
F.399
Burner in a fault state
F.400
Burner in a fault state
F.401
Burner in a fault state
F.402
Burner in a fault state
F.403
Burner in a fault state
F.404
Burner in a fault state
F.405
Burner in a fault state
F.406, F.408,
Burner in a fault state
F.410
F.416
Burner locked out
F.417, F.418
Burner in a fault state
Cause
BCU burner control unit
faulty
Earth fault, ionisation cur-
rent. BCU burner control
unit faulty.
BCU burner control unit
faulty
IO electrode earth fault,
BCU burner control unit
faulty
BCU burner control unit
faulty
IO electrode earth fault,
BCU burner control unit
faulty
BCU burner control unit
faulty
IO electrode earth fault,
BCU burner control unit
faulty
BCU burner control unit
faulty
Ionisation electrode earth
fault, BCU burner control
unit faulty
BCU burner control unit
faulty
Ionisation electrode earth
fault, BCU burner control
unit faulty
BCU burner control unit
faulty
Flue gas temperature sen-
sor incorrectly positioned
BCU burner control unit
faulty
Troubleshooting
Measures
Replace BCU burner control unit:
See page 100.
Reset the appliance.
Check ionisation electrode and
connecting cable. If fault persists,
replace BCU burner control unit:
See page 100.
Reset the appliance.
Replace BCU burner control unit:
See page 100.
Reset the appliance.
Check ignition electrode for earth
fault. If fault persists, replace BCU
burner control unit: See page 100.
Reset the appliance.
Replace BCU burner control unit:
See page 100.
Reset the appliance.
Check IO electrode for earth fault.
If fault persists, replace BCU burn-
er control unit: See page 100.
Reset the appliance.
Replace BCU burner control unit:
See page 100.
Reset the appliance.
Check IO electrode for earth fault.
If fault persists, replace BCU burn-
er control unit: See page 100.
Reset the appliance.
Replace BCU burner control unit:
See page 100.
Reset the appliance.
Check IO electrode for earth fault.
If fault persists, replace BCU burn-
er control unit: See page 100.
Reset the appliance.
Replace BCU burner control unit:
See page 100.
Reset the appliance.
Check IO electrode for earth fault.
If fault persists, replace BCU burn-
er control unit: See page 100.
Reset the appliance.
Replace BCU burner control unit:
See page 100.
Reset the appliance.
Fit flue gas temperature sensor
correctly. See "Repairs".
Carry out mains reset after fault
has been remedied.
Replace BCU burner control unit:
See page 100.
Reset the appliance.
89