Viessmann B2TF Installation And Service Instructions Manual page 50

Gas condensing storage combi boiler with 7 inch colour touchscreen
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Checking anode connection and anode earth current with anode tester
Check that the earth cable is connected to the protec-
tive magnesium anode.
Note
We recommend checking the function of the protective
magnesium anode annually. This function test can be
carried out without interrupting operation, by measur-
ing the earth current with an anode tester.
A
Fig. 41
1. Remove cover
(two-part design up to 26 kW).
A
2. Remove earth cable
B
Draining the boiler on the DHW side
50
C B
from tab
.
C
3. Connect tester (up to 5 mA) in series between tab
C
and earth cable
B
If the current measures > 0.3 mA the protective
magnesium anode is OK.
If the current measures < 0.3 mA or if there is no
current at all, inspect the protective magnesium
anode visually (see page 52).
1. Shut off the DHW supply upstream of the appli-
ance.
.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 222-f

Table of Contents