Installation
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100mm under the unit°Øs legs before being fixed.
• The outdoor unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
For outdoor units of 23kW or
above should not be supported
only by the corner supports.
Outdoor units of 14.5, 16kW
can be supported only by the
corner supports.
The location of the Anchor bolts
Chassis
UX1
UX2
UX3
18
Outdoor Unit
Outdoor Unit Capacity
H/P
8~12HP
10~14HP
14~20HP
16~20HP
Needed for outdoor units of 23kW or above
Center of the Unit
Needed for outdoor units of 23kW or above
Center of the Unit
Unit : mm
A(mm)
C/O
6~8HP
B(mm)
620
920
1240
1102
497
792