Hoshizaki KML-500MAJ Instruction Manual page 25

Low-profile modular crescent cuber
Hide thumbs Also See for KML-500MAJ:
Table of Contents

Advertisement

3) Evacuate through the Schrader access ports on the Parker quick connect couplings and
charge with R-404A refrigerant vapor to a pressure of 15 to 30 PSIG. Go to step 2 in
"II.G.5.a) Factory Line Set Installation."
b) Field Fabricated Line Set Installation
1) Route the copper tube liquid line and copper tube discharge line (see "II.G.4 Line
Set Size and Refrigerant Charge" for details) from the remote condenser unit to the
icemaker. Leave a service loop behind the icemaker to allow the icemaker to be pulled
out for service. See Fig. 12.
• Ensure that there are no traps and no kinks in the line set. The service loop is not
considered an oil trap.
• Do not coil extra line set. Fabricate the line set to the proper length.
2) Insulate the two copper tubes separately.
3) Install Parker quick connect couplings on each end. OS-QUICK, a universal quick
connect coupling kit available as optional equipment from Hoshizaki America, is
recommended. NOTICE! Before brazing, remove the Schrader valve core from the
access port. When brazing, protect the coupling by using a wet cloth to prevent
the coupling from overheating. Do not use silver alloy or copper alloy containing
arsenic.
4) Allow the coupling to cool, then replace the Schrader valve core.
5) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace
of refrigerant to the lines through the Schrader access ports on the Parker quick
connect couplings (if using an electronic leak detector), and then raise the pressure
using nitrogen gas (140 PSIG). WARNING! Do not use R-404A as a mixture with
pressurized air for leak testing.
6) Evacuate through the Schrader access ports on the Parker quick connect couplings and
charge with R-404A refrigerant vapor to a pressure of 15 to 30 PSIG.
7) Connect the refrigerant lines to the appropriate male fittings on the remote condenser
unit first and then at the icemaker. Make a proper connection as follows:
a. Remove the protective covers from the male fitting and female coupling.
b. Apply Polyol Ester (POE) refrigerant oil or Parker Super O Lube to the entire male
fitting, including O-ring, diaphragm, and threads, before making the connection.
See Fig. 13. NOTICE! Do not use thread sealant on the fittings. Use POE
refrigerant oil or Parker Super O Lube only.
c. Make sure the male fitting and female coupling are properly aligned, then start the
connection by hand to ensure that it is not cross threaded.
d. Tighten the connection with a wrench until it is tight. At this point, the nut has
covered most of the threads on the male fitting.
e. Mark a reference line on the female coupling and the remote condenser unit or
icemaker panel. Using a backup wrench on the back of the female coupling, tighten
the six-sided nut of the female coupling an additional 1/6 turn. See Fig. 14.
8) If the line set exceeds 66 feet, see "II.G.4. Line Set Size and Refrigerant Charge" for
proper charging of the appliance.
NOTICE
25