Page 1
Burner Specification & Data Sheet Figure 1 Model WCR 4.00 Burner B(R) C(R) Model Number WCR1 34.13 5.56 14.50 WCR2 39.13 6.13 14.00 WCR3 44.00 7.00 15.25 WCR4 50.00 7.31 17.69 Water & Steam Boilers – Series 2 For Gas, Light Oil, & Gas/Light Oil – Fired Burners Note: Add .38 to “H”...
Page 2
Weil-McLain 88 Water and Steam Boilers — Series 2 — Burner specifications and settings Table 1 Burner data Burner Input Positive Burner Model Designation Boiler Pressure Model In Firebox No. 2 Oil Number In. W.C. 488R 0.80 WCR1-G-12 WCR1-OS 1,010 0.80...
Page 3
Burner Specification & Data sheet — Power Flame Gas/Oil Burners — Model WCR Burner specifications and settings Table 2 Gas train components and flame safeguards Gas Pressure Initial Low Fire Required At Gas Pressure Damper Setting Manifold Control Inlet Boiler Drop Thru Inches Pressure...
Page 4
“C” models provide interrupted pilot and RUN/TEST switch. RM7897 provides same as above with post-purge. Monitors the oil or gas burner flame, provides pre-purge and post-purge programming, provides switching necessary to allow RM7840L, E110/EPD170 firing rate motor to be driven to both low fire and high fire positions, prevents start-up if pre-ignition interlocks are open and has low fire start proving circuit.