Beckett Warning–Notice to Owner Please read and follow all instructions on Page 3 in this manual regarding your responsibilities in caring for your heating equipment Contact a qualified service agency for installation and start-up. Incorrect Installation, adjustment, or misuse of this burner could result in severe personal injury, death or substantial property damage.
Hazard Defi nitions and Owner’s Information Information To Be Used Only By Qualifi ed Service Technicians Weil McLain Burner Specifi cation General Information ... 5 Certifi cations/Approvals…………………………………………………………..5 Notice Special Requirements ... 6 Inspect/Prepare Installation Site Clearances to Burner and Appliance ... 7 Inspect Chimney or Direct Vent System ...
Table 1. Burner Confi gurations The table below provides burner specifi cations and starting air settings for NX burners applied to Weil-McLain Model UO boilers. Follow all instructions in this burner manual, the boiler manual and the fuel pump literature to install, setup and service the burner.
General Specifi cations State and local approvals are shown on burner rat- ing label mounted on the burner housing. For recommended installation practice in Canada, refer to the latest version of CSA Standard B139 & B140. Figure 1. Burner label location Page 6 Notice Special Requirements •...
Inspect/Prepare Installation Site Clearances to Burner and Appliance • Provide space around burner and appliance for ease of service and maintenance. Check the minimum clearances against those shown by the appliance manufacturer and by ap- plicable building codes. Inspect Chimney or Direct Vent System •...
Part Number 5199OU), refer to the instruction sheet supplied with the adapter. This kit allows combustion air to be piped directly to the burner. The NX outside air adapter kit may also be used for chimney vent applications that require outside combustion air.
S109 The NX burner has a reduced diameter air tube, precision-designed air throttle cup and combus- tion head for improved performance. This de- sign provides very accurate control of the air/fuel ratio, but the light reaching the cad cell through small holes in these components is limited.
Start the Burner Start the Burner and Set Combustion Start-up and Initial Settings • Open the shutoff valves in the oil supply line to the burner. Referencing Figure 5 verify and/or set the Head/ Air Adjustment Pointer to the value shown in Table 1.
Warning–Check for Excess Fuel Accumulation. Do not attempt to start the burner when excess fuel or vapor has accumulated in the appliance. Starting the burner under these conditions could result in a puffback of hot combustion gases, high smoke levels, or otherwise hazardous operation.
Professional Maintenance Trained Service Technician’s Regular Maintenance While performing routine maintenance check the following. Replace the oil supply line fi lter. The line fi lter car- tridge must be replaced to avoid contamination of the fuel pump and nozzle. • Inspect the oil supply system.
• Nozzle Installation Obtain a nozzle having the capacity, spray angle, and pattern specifi ed in the appliance manufac- turer’s information or Beckett OEM Specifi cation Guide, Part # 6711. Make certain the correct nozzle is selected for the actual fuel pump pressure. See Table 1. Perform the following steps when replacing a noz- zle.
NOTICE The NX burner has a reduced diameter air tube, precision-designed air throttle cup and combus- tion head for improved performance. This de- sign provides very accurate control of the air/fuel ratio, but the light reaching the cad cell through small holes in these components is limited.
• Blower Wheel Replacement For installation or replacement of a blower wheel, insure that there is a space between the blower wheel and the motor face of 0.115”. Refer to Figure Figure 10. – Blower wheel assembly WM 550-141-996/1105 RWB 6104WMNX R1005 Professional Maintenance SK9670 Page 17...
Professional Maintenance Replacement Parts Diagram SK967102 SK9804B SK9803B Beckett For best performance specify genuine replacement parts Page 18 WM 550-141-996/1105 RWB 6104WMNX R1005...
60 months from the date of manufacture for Residential Burners and 18 months from the date of manufacture for Commercial and Specialty Burners. Residential burner models include: AF, AFG, AFII, NX, SF, SR and SMG. Commercial burner models include: CF375, CF500, CF800, CF1400, CF2300A, CF2500, CF3500A, CG10, CG15, CG25 and CG50.