To Connect The Refrigerant Piping To The Outdoor Unit - Daikin RXYSQ6T7Y1B9 Installer's Manual

Vrv iv-s system air conditioner
Hide thumbs Also See for RXYSQ6T7Y1B9:
Table of Contents

Advertisement

6 Installation
a
Service port
b
Stop valve cover
c
Hexagon hole
d
Shaft
e
Seal
To open the stop valve
1 Remove the stop valve cover.
2 Insert a hexagon wrench into the stop valve and turn the stop
valve counterclockwise.
3 When the stop valve cannot be turned any further, stop turning.
Result: The valve is now open.
2
3
1
4
To close the stop valve
1 Remove the stop valve cover.
2 Insert a hexagon wrench into the stop valve and turn the stop
valve clockwise.
3 When the stop valve cannot be turned any further, stop turning.
Result: The valve is now closed.
Closing direction:
To handle the stop valve cover
▪ The stop valve cover is sealed where indicated by the arrow. Take
care not to damage it.
▪ After handling the stop valve, make sure to tighten the stop valve
cover securely. For the tightening torque, refer to the table below.
▪ Check for refrigerant leaks after tightening the stop valve cover.
To handle the service port
▪ Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
▪ After handling the service port, make sure to tighten the service
port cover securely. For the tightening torque, refer to the table
below.
▪ Check for refrigerant leaks after tightening the service port cover.
Installer and user reference guide
18
Tightening torques
Stop valve
Tightening torque N•m (turn clockwise to close)
size (mm)
Valve body Hexagonal
wrench
Ø9.5
5.4~6.6
4 mm
Ø15.9
13.5~16.5
6 mm
6.4.8
To connect the refrigerant piping to the
outdoor unit
NOTICE
Be sure that the field installed piping does not touch other
pipes, the bottom panel or side panel. Especially for the
bottom and side connection, be sure to protect the piping
with suitable insulation, to prevent it from coming into
contact with the casing.
1 Do the following:
▪ Remove the service cover (a) with screw (b).
▪ Remove the piping intake plate (c) with screw (d).
a
b
c
d
2 Choose a piping route (a, b, c or d).
d
a
c
b
3 If you have chosen the downwards piping route:
▪ Drill (a, 4×) and remove the knockout hole (b).
▪ Cut out the slits (c) with a metal saw.
a
b
4× Ø6 mm
c
c
4 Do the following:
▪ Connect the liquid pipe (a) to the liquid stop valve.
▪ Connect the gas pipe (b) to the gas stop valve.
b
a
▪ Connect the gas piping accessories (c, c1, d, e), and cut
them to the required length (e1). This is necessary because
the size of the gas stop valve is Ø15.9 while the piping
between outdoor unit and first refrigerant branch kit is Ø19.1.
Shaft
Cap (valve
Service
lid)
port
13.5~16.5
11.5~13.9
22.5~27.5
RXYSQ6T7Y1B9
VRV IV-S system air conditioner
4P404677-1A – 2016.03

Advertisement