Relating communication parameters
Following parameters should be set or changed if necessary.
• Baud rate (, )... Shipment setting = : 19200bps
Baud rate of all inverters in the network (master and slave) should be same network.
• Parity () ... Shipment setting = : Even parity
Parity of all inverters in the network (master and slave) should be same network.
• Communication time-out time() ... Shipment setting = 
Operation is continued by the last received command value in the case of a communication break-
down. To stop the operation of inverter, provide a communication time-out time (ex. =
) to the slave inverters. The master inverter does not trip even though the communication break-
ond
down happens. To trip the master inverter, provide an interlock mechanism by installing a FL fault
relay point or the like from the slave side.
• Frequency point selection (, )
Adjusted to the system.
See chapter "6.1 Speed proportional control" for details.
Setting example of parameters (2-wire RS485 communication)
Parameters relating to the master side (example)

Master (transmission of output frequency
(%) (100% at FH))

Selection of communication protocol
(Toshiba inverter protocol)
Communication baud rate

(ex. 19200bps)
Parity (even parity)

Example: Panel

 Example: RR/S4 input
<During torque control>

Master (sends a torque command)
Parameters relating to the slave side (example)
 Slave (If the master inverter trips, all slave inverters stop
operating.)
Selection of communication protocol

(Toshiba inverter protocol)
Communication time-out (ex. 1 second)

Communication baud rate (same to the master side)

Parity (same to the master side)

Terminal block (ex. Driven by F, ST)

( Run and stop of operation is controlled with the frequency
reference value by setting the "run frequency".)

Operation panel RS485 (2-wire) communication input

2-wire RS485
?
Adjusted to the system Point 1 setting (%)
 ?
Ditto
 ?
Ditto
 ?
Ditto
<During torque control>
RS485 communication input

Load sharing gain input mode selection (ex. Operation

panel input enabled)
 Panel load sharing gain (ex. Sharing of half of the com-
mand value)
36
E6581315
sec-
Point 2 frequency (Hz)
Point 2 setting (%)
Point 2 frequency (Hz)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tosvert vf-as1 series

Table of Contents