Inverter → Computer
At time of broadcast communication of the binary mode, returning of data is not executed except for
the inverter to be returned (inverter number 00H) and when the inverter number is not matched. This
is because there will be a risk that the returned data may be deformed.
1) Normal processing
Omissible
(3.5
Start
INV
CMD
Number
bytes
Code
of Read
No.
"Y"
Blank)
"/"
1. 2FH "/" (1 byte)
2. INV-NO (1Byte)
3. CMD(1Byte)
4. Number of read data groups (1 byte)
5. Write status (1 byte) : Return 00H to 03H.
6. Read data1 - 5 (2 bytes)
7.SUM(1Byte)
Example
(When set as follows:  =  (Command information 1),  =  (frequency command),
 =  (status information), =  (output frequency),  =  (output current),  =  (output
voltage) and  =  (alarm information)
Computer → Inverter:2F 58 02 05 C4 00 17 70 D9
Inverter → Computer:2F 59 05 03 00 00 00 00 00 00 00 00 00 00 90 (When parameter is not set)
Inverter → Computer:2F 59 05 00 40 00 00 00 00 00 00 00 00 00 CD CD (When parameter is set)
Inverter → Computer:2F 59 05 00 64 00 17 70 1A 8A 24 FD 00 00 3D (During operation at 60Hz)
Number of read data groups x 2 bytes
Write
Read
Read
Status
data1
data1
Data
high
low
Groups
Checksum area
:Start code in binary mode
:Inverter number・・・00H to 3FH
If the inverter number matches up with that specified from the operation panel, data will
be returned from the inverter. If the inverter number does not match, the data will be
judged invalid and no data will be returned.
Communication data will be invalidated and data will not be returned either if the in-
verter number does not match. (Inverter number is considered matched if it is omitted
during reception)
:'Y' (Block communication command [monitoring])
Lowercase letter 'y' during an inverter trip, including standing by for retrying and during
a trip.
: Return the number of data groups to be read (00H to 05H).
* Failing to write in the specified parameter in the number of write data groups, set "1"
in the corresponding bit for the parameter failed to write. (See below.)
Bit Position
7
Data Type
: Return according to the number of read data groups. "0000H" is returned as dummy
data if "0" is selected as a parameter.
Read data1: Data selected by . Read data2: Data selected by .
Read data3: Data selected by . Read data4: Data selected by .
Read data5: Data selected by .
: Checksum (Cannot be omitted) 00H to FFH
Lower two digits (1 byte) of total sum from start code of return data to read data.
Read
Read
Read
Read
Read
data2
data2
data3
data3
data4
high
low
high
low
6
5
4
3
2

15
Read
Read
Read
SUM
data4
data5
data5
high
low
high
low
1
0

E6581315
(3.5
bytes
Blank)