Bard YA423 Installation Instructions Manual

Wall mounted package air conditioners

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
WALL MOUNTED
PACKAGE AIR CONDITIONERS
MODELS
YA423
YA484
YA602
Manual :
2100-459
Supersedes:
Date:
06-20-05
© Copyright 2005

Advertisement

Table of Contents
loading

Summary of Contents for Bard YA423

  • Page 1 INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS YA423 YA484 YA602 Manual : 2100-459 Supersedes: Date: 06-20-05 © Copyright 2005...
  • Page 2: Table Of Contents

    Contents Start Up Getting Other Information and Publications Important Installer Note ......... 14 High Pressure Switch ..........14 Wall Mount General Information Three Phase Scroll Compressor Start Up ....14 Heat Pump Wall Mount Model Nomenclature ..2 Phase Monitor ............14 Shipping Damage ............
  • Page 3: Getting Other Information And Publications

    GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these at THESE PUBLISHERS: your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard.
  • Page 4: Wall Mount General Information

    WALL MOUNT GENERAL INFORMATION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE – REVISIONS CONTROL MODULES MODEL NUMBER (See Chart Below) CAPACITY COIL OPTIONS 38 - 3 Ton X - Standard 42 - 3½ Ton VOLTS & PHASE 1 - Phenolic Coated Evaporator 48 - 4 Ton A - 230/208/60/1 COLOR OPTIONS...
  • Page 5: Figure 1 Unit Dimensions

    Manual 2100-459 Page...
  • Page 6: Table 2 Electrical Specifications

    TABLE 2 ELECTRICAL SPECIFICATIONS & Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75° C copper wire. All wiring must conform to NEC and all local codes. These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), article 310 for power conductor sizing.
  • Page 7: Shipping Damage

    & Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75° C copper wire. All wiring must conform to NEC and all local codes. These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), article 310 for power conductor sizing.
  • Page 8: Duct Work

    Any grille that meets with 5/8 inch louver criteria may CONDENSATE DRAIN be used. It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be A plastic drain hose extends from the drain pan at the installed when no return duct is used.
  • Page 9: Installation Instructions

    INSTALLATION INSTRUCTIONS WALL MOUNTING INFORMATION WARNING 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3. 2. On wood frame walls, the wall construction must be Failure to provide the 1/4 inch clearance strong and rigid enough to carry the weight of the between the supply duct and a combustible unit without transmitting any unit vibration.
  • Page 10: Figure 3 Mounting Instructions

    Manual 2100-459 Page...
  • Page 11: Figure 4 Electric Heat Clearance

    FIGURE 4 ELECTRIC HEAT CLEARANCE SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES. MIS-277 WARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting.
  • Page 12: Figure 5 Wall Mounting Instructions

    FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS WALL STRUCTURE FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION SUPPLY AIR SUPPLY AIR SUPPLY AIR OPENING OPENING OPENING RETURN AIR RETURN AIR RETURN AIR OPENING OPENING OPENING BOTTOM MOUNTING BRACKET.
  • Page 13: Figure 7 Common Wall Mounting Installations

    FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT CLOSET INSTALLATION FALSE WALL INSTALLATION MIS-550 Manual 2100-459 Page...
  • Page 14: Wiring - Main Power

    WIRING – MAIN POWER WIRING – LOW VOLTAGE WIRING Refer to the unit rating plate for wire sizing information 230/208V, 1 phase and 3 phase equipment dual primary and maximum fuse or “HACR” type circuit breaker voltage transformers. All equipment leaves the factory size.
  • Page 15: Figure 8 Unit 24V Terminal Board

    FIGURE 8 UNIT 24V TERMINAL BOARD Manual 2100-459 Page...
  • Page 16: Start Up

    START UP IMPORTANT INSTALLER NOTE PHASE MONITOR For improved start up performance wash the indoor coil All units with three phase scroll compressors are with a dish washing detergent. equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal. HIGH PRESSURE SWITCH The phase monitor in this unit is equipped with two LEDs.
  • Page 17: Sequence Of Operation

    YA484 and YA602 models covered by this manual and conditioner or heat pump unit model. The is optional on the YA423 model. The compressor lockout features, both soft and manual, are a control is an anti-short cycle/lockout timer with high and function of the Compressor Control Module.
  • Page 18: Figure 9 Fan Blade Setting

    TROUBLESHOOTING FAN BLADE SETTING DIMENSIONS 4. Unwire condenser fan motor. Shown in Figure 9 is the correct fan blade setting 5. Slide complete motor, fan blade, and shroud dimension for proper air delivery across the outdoor assembly out the left side of the unit. coil.
  • Page 19: Table 8 Recommended Airflow

    TABLE 8 RECOMMENDED AIRFLOW f r i TABLE 9 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY Values shown are for units equipped with standard 1-inch throwaway filter or 1-inch washable filter. Derate ESP by .15 for 2-inch pleated filters. Manual 2100-459 Page...
  • Page 20: Pressure Table

    TABLE 10 PRESSURE TABLE COOLING Air Temperature Entering Outdoor Coil °F Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.
  • Page 21: Optional Accessories

    TABLE 11 OPTIONAL ACCESSORIES l a i i t n t a l i t n t a l i t n t a l t i u l l u t i u t i u t i u Manual 2100-459 Page...

This manual is also suitable for:

Ya484Ya602