6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Models:ROSH18AXFWJ and ROSH24AXFWJ

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than outdoor
unit *2
HEATING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than outdoor
unit *2
Height difference H
1
*
H
Outdoor unit
m
5
ft
16
30
98
20
65
10
32
7.5
24
5
16
0.992 0.992 0.992 0.968 0.971 0.968 0.963
0
0
0.998 1.000 1.000 0.976 0.979 0.976 0.971
-5
-16
0.998 1.000 1.000 0.976 0.979 0.976 0.971
-7.5
-24
-10
-32
-20
-65
-30
-98
5
m
ft
16
30
98
20
65
10
32
7.5
24
5
16
0.986 1.000 0.991 0.872 0.816 0.756 0.686
0
0
0.986 1.000 0.991 0.872 0.816 0.756 0.686
-5
-16
0.981 0.995 0.986 0.868 0.812 0.752 0.683
-7.5
-24
-10
-32
-20
-65
-30
-98
- 40 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length
7.5
10
20
24
32
65
-
-
-
-
-
-
-
0.945 0.947 0.945 0.940
-
-
0.984 0.961 0.963 0.960 0.956
-
0.988 0.988 0.965 0.967 0.964 0.959
-
1.000 1.000 0.976 0.979 0.976 0.971
-
-
1.000 0.976 0.979 0.976 0.971
-
-
-
0.976 0.979 0.976 0.971
-
-
-
-
Pipe length
7.5
10
20
24
32
65
-
-
-
-
-
-
-
0.872 0.816 0.756 0.686
-
-
0.991 0.872 0.816 0.756 0.686
-
1.000 0.991 0.872 0.816 0.756 0.686
-
0.993 0.983 0.866 0.810 0.750 0.681
-
-
0.981 0.864 0.808 0.748 0.679
-
-
-
0.855 0.799 0.740 0.672
-
-
-
-
2
*
30
40
50
98
131
164
0.932 0.929 0.924
0.979 0.976 0.971
30
40
50
98
131
164
0.816 0.756 0.686
0.791 0.733 0.665