Omron K8DT-VW Quick Start Manual page 11

Single-phase overvoltage/undervoltage relay
Table of Contents

Advertisement

Recommended Ferrules and Crimp Tools
Recommended ferrules
Applicable
Stripping
Ferrule
length
wire
Conductor
(mm)
Length
(Ferrules
2
(mm
)
(AWG)
(mm)
used)
8
10
0.25
24
10
12
8
10
0.34
22
10
12
8
10
0.5
20
10
12
8
10
0.75
18
10
12
8
10
1/1.25
18/17
10
12
8
10
1.25/1.5 17/16
10
12
Recommended crimp tool
Note: 1. Make sure that the outer diameter of the wire coating is
smaller than the inner diameter of the insulation sleeve of
the recommended ferrule.
2. Make sure that the ferrule processing dimensions conform
to the following figures.
8 to 10 mm
1.9 mm max.
2.6 mm max.
Recommended Flat-blade Screwdriver
Use a flat-blade screwdriver to connect and remove wires.
Use the following flat-blade screwdriver.
The following table shows manufacturers and models as of 2015/Dec.
Side
Front
2.5 mm dia.
0.4 mm
2.5 mm
Model
×
ESD 0,40
2,5
×
SZS 0,4
2,5
×
2,5 *
SZF 0-0,4
×
×
0.4
2.5
75 302
×
AEF.2,5
75
210-719
×
×
SDI 0.4
2.5
75
* OMRON's exclusive purchase model XW4Z-00B is available to
×
order as SZF 0-0,4
2,5 (manufactured by Phoenix Contact).
Recommended ferrules
Phoenix Contact
Weidmuller
Wago
product
product
product
AI 0,25-8
H0.25/12
216-301
AI 0,25-10
---
---
AI 0,34-8
H0.34/12
216-302
AI 0,34-10
---
---
AI 0,5-8
H0.5/14
216-201
AI 0,5-10
H0.5/16
216-241
AI 0,75-8
H0.75/14
216-202
AI 0,75-10
H0.75/16
216-242
AI 1-8
H1.0/14
216-203
AI 1-10
H1.0/16
216-243
AI 1,5-8
H1.5/14
216-204
AI 1,5-10
H1.5/16
216-244
CRIMPFOX6
CRIMPFOX6T-F
PZ6 roto
Variocrimp4
CRIMPFOX10S
Manufacturer
Wera
Phoenix Contact
Wiha
Facom
Wago
Weidmuller
EN/IEC Standard Compliance
• Refer to the contents of this datasheet for cable selection and other
conditions for compliance with EMC standards.
Precaution on EN Standard Compliance
The K8DT complies with EN 60947-5-1 when it is built into a panel,
but observe the following handling methods to ensure compliance
with the requirements of this standard.
Wiring
Overvoltage category III
Pollution degree 2
• Open-frame Device
• If basic, double, or reinforced insulation is required, use the basic,
double, or reinforced insulation defined in IEC 60664 that is
suitable for the maximum applied voltage for the clearance, solid
insulation, and other factors.
• There is basic insulation between the power supply terminals and
input terminals.
• There is basic insulation between the power supply terminals and
output terminals.
• There is basic insulation between the input terminals and output
terminals.
• Operating section must have reinforced or double insulation.
• The sides of the case are not isolated.
• Connect the output contacts (contacts with different polarity) so
that they reach the same potential.
Reinforced insulation
(Double insulation)
K8DT-VW
Not isolated
11