Inverter Radiation Fin Temperature Abnormality - Daikin VRV X RXQ6-48ANR Series Service Manual

Cooling only 50/60 hz
Table of Contents

Advertisement

Troubleshooting by Error Code

5.47 Inverter Radiation Fin Temperature Abnormality

Applicable
All outdoor unit models
Models
P4
Error Code
Method of Error
Detect the resistance of the following thermistors during the compressor stops running:
Detection
(1) Radiation fin thermistor
(2) Thermistor located in PCB circuit
Error Decision
When the resistance of the thermistor comes to a value equivalent to open or short circuit.
Conditions
Error is not decided while the unit operation is continued.
P4 will be displayed by pressing the inspection button.
Supposed
 Defective radiation fin temperature thermistor
Causes
 Defective inverter PCB
 Defective fan PCB
 Defective compressor
 Defective fan motor