Panasonic S-M20PY3E Operating Instructions Manual page 15

Table of Contents

Advertisement

Model Name
Europe
Power source
kW
Cooling capacity
BTU/h
kW
Heating capacity
BTU/h
Sound pressure level
dB(A)
(Cooling / Heating)
Sound power level
dB(A)
(Cooling / Heating)
Unit dimensions
mm
(H×W×D)
Net weight
kg
Operation condition temperature range
• Cooling mode : -10°C~43°C DB • Heating mode : -15°C~24°C DB
Rated conditions
Cooling : Indoor intake air temp. 27°C DB / 19°C WB. Outdoor intake air temp. 35°C DB.
Heating : Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB / 6°C WB.
U-100PZ2E5
220 - 230 - 240 V~ 50 Hz
10.0
34,100
10.0
34,100
52 / 52
70 / 70
996×980×370
90
U-100PZ2E8
380 - 400 - 415 V 3N~ 50 Hz
10.0
34,100
10.0
34,100
52 / 52
70 / 70
996×980×370
90
15