Download Print this page

Pcb - Daikin FDXV41NVLT Service Manual Removal Procedure

4.1/5.0/6.3/7.1 kw class

Advertisement

PCB

2. PCB
Warning
Step
1. Remove the electrical box
cover.
1
Remove the 2 screws.
2
Lift up the electrical box
cover to unfasten the 2
hooks and remove it.
2. Remove the PCB.
1
Pull out the 4 terminals
from the terminal board.
4
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Procedure
Right side
Electrical box
cover
Hook
Terminal board
1
2
Points
(R22686)
When reassembling, make
sure that the 2 hooks are
securely fastened.
(R22687)
1: front, Black
3 4
2: front, White
3: front, Red
4: front, Earth / ground wire:
green / yellow
(R22688)
Removal Procedure
Si071562E