Installing the Device
2.6 Connecting Power
1
2
3
Figure 2.5
2.6

Connecting Power

The RUGGEDCOM RSG2100F supports a single or dual redundant AC and/or DC
power supplies.
The RUGGEDCOM RSG2100F can be equipped with either a screw-type or pluggable
terminal block, which provides power to both power supplies. The screw-type
terminal block is installed using Phillips screws and compression plates, allowing
either bare wire connections or crimped terminal lugs. Use #6 size ring lugs for
secure, reliable connections under severe shock or vibration.
Electrical hazard – risk of power supply failure or damage to the device
Make sure power input to the device is within the specified input range. If power
input is too high, damage to the power supply may occur. If power input is too low,
damage to the device may occur. For information about the nominal input range for
the device, refer to
Note
14
1
Normally Open
Common
Normally Closed
Failsafe Alarm Relay Wiring
NOTICE
"Power Supply Specifications (Page
For maximum redundancy in a dual power supply configuration, use two
independent power sources.
Use minimum #16 gage copper wiring when connecting terminal blocks.
For 100-240 VAC rated equipment, an appropriately rated AC circuit breaker
must be installed.
A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
It is recommended to provide a separate circuit breaker for each power supply
module.
3
2
31)".
RUGGEDCOM RSG2100F
Installation Manual, 04/2022, C79000-G8976-1344-11