Indoor Unit Fixing; Drainage - Toshiba RAS-M05N4KVSG-E Installation Manual

Hide thumbs Also See for RAS-M05N4KVSG-E:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
In case of right or left piping
• After scribing slits of the back body
with a knife or a making-off pin, cut
them with a pair of nippers or an
equivalent tool.
In case of bottom right or bottom left piping
• After scribing slits of the back body
with a knife or a making-off pin, cut
them with a pair of nippers or an
equivalent tool.
Left-hand connection with piping
• Bend the connecting pipe so that it is laid within 43 mm above the wall
surface. If the connecting pipe is laid exceeding 43 mm above the wall
surface, the indoor unit may unstably be set on the wall.
When bending the connecting pipe, make sure to use a spring bender so
as not to crush the pipe.
Bend the connecting pipe within a radius of 30 mm.
To connect the pipe after installation of the unit (fi gure)
260 mm
210 mm
R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the
connecting pipes to the auxiliary pipes and wrap the facing tape around
them.
CAUTION
• Bind the auxiliary pipes (two) and connecting cable with facing tape
tightly. In case of leftward piping and rear-leftward piping, bind the
auxiliary pipes (two) only with facing tape.
Auxiliary pipes
Installation plate
• Carefully arrange pipes so that any pipe does not stick out of the rear
plate of the indoor unit.
• Carefully connect the auxiliary pipes and connecting pipes to one
another and cut off the insulating tape wound on the connecting pipe
to avoid double-taping at the joint; moreover, seal the joint with the
vinyl tape, etc.
• Since dewing results in a machine trouble, make sure to insulate both
connecting pipes. (Use polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.
Slit
Slit
(To the forefront of fl are)
Gas side
Liquid side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Indoor unit
Connecting cable

Indoor Unit Fixing

1. Pass the pipe through the hole in the wall and hook the indoor unit on the
installation plate at the upper hook.
2. Swing the indoor unit to right and left to confi rm that it is fi rmly hooked up
on the installation plate.
3. While pressing the indoor unit onto the wall, hook it at the lower part on
the installation plate. Pull the indoor unit toward you to confi rm that it is
fi rmly hooked up on the installation plate.
1
2
Hook
• For detaching the indoor unit
from the installation plate, pull
the indoor unit toward you while
pushing its bottom up at the
specifi ed parts.
1. Run the drain hose sloped downwards.
NOTE
• The hole should be made at a slight downward slant on the outdoor side.
Do not rise the
drain hose.
50 mm
or more
2. Put water in the drain pan and make sure that the water is drained out of
doors.
3. When connecting extension drain hose, insulate the connecting part of
extension drain hose with shield pipe.
Drain hose
CAUTION
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed
to drain water collected from dew, which forms
on the back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other
parts at a height above the drain guide.
10
Hook here.
1
Installation plate
Push

Drainage

Do not form the
drain hose into
a wavy shape.
Do not put the
Do not put the
drain hose end
drain hose end
into water.
in the drainage ditch.
Shield pipe
Extension drain hose
Inside the room
Space for pipes
Press
(unhook)
Push
Wall
Drain
guide