York MILLENNIUM Y22 Installation Manual page 55

25, 30 & 40 ton
Table of Contents

Advertisement

102777-YIM-E-0206
TABLE 28: FAN PERFORMANCE - 40 TON
AIRFLOW (CFM)
RPM
8000
774
9000
784
10000
794
11000
804
12000
814
13000
825
14000
837
15000
851
16000
866
17000
882
18000
900
1.
Fan performance is based on wet evaporator coils, clean 2-inch throwaway filters and system/cabinet effects at standard air den-
sity and 0 degree elevation.
2.
Refer to Tables 29, 57 and 66 for component additions and deductions to fan performance tables.
3.
BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.
Unitary Products Group
1 2
(Continued)
Available External Static Pressure (IWG)
3.2
3.4
3
RPM
BHP
BHP
8.3
797
9.3
806
10.3
815
11.0
11.6
824
12.2
12.9
835
13.6
14.4
846
15.1
16.0
858
16.8
17.8
871
18.6
19.7
886
20.5
21.9
901
22.7
24.2
-
3.6
3
3
RPM
BHP
8.8
817
9.4
9.8
826
10.4
836
11.6
845
12.9
855
14.3
866
15.8
878
17.5
891
19.4
905
21.4
919
23.6
-
-
-
3.8
3
RPM
RPM
BHP
837
9.9
857
846
11.0
866
856
12.3
876
865
13.6
886
876
15.0
896
886
16.6
906
898
18.3
917
910
20.2
928
923
22.2
941
937
24.5
-
-
-
-
4.0
3
BHP
10.5
11.6
12.9
14.2
15.7
17.3
19.1
21.0
23.1
-
-
55