FB3000 Remote Terminal Unit (RTU)
HART
®
I/O Module
Field Installation Guide
For Part Numbers:
Remote Automation Solutions
3HRT04
3HTSG4
FB3000 RTU HART
®
I/O Module Field Installation Guide
D301918X012
June 2021

Advertisement

loading

Summary of Contents for Emerson HART FB3000

  • Page 1 FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 FB3000 Remote Terminal Unit (RTU) HART ® I/O Module Field Installation Guide For Part Numbers: 3HRT04  3HTSG4  Remote Automation Solutions...
  • Page 2 Our full-time professional instructors can conduct classroom training at several of our corporate offices, at your site, or even at your regional Emerson office. You can also receive the same quality training via our live, interactive Emerson Virtual Classroom and save on travel costs. For our complete schedule and further information, contact the Remote Automation Solutions Training Department at 800-338-8158 or email us at education@emerson.com.
  • Page 3 FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 HART ® Input/Output Channels (3HRT04/3HTSG4) The FB3000 RTU supports a HART ® (Highway Addressable Remote Transducer) module with four (4) channels. This allows the FB3000 to communicate with external HART devices such as transmitters.
  • Page 4 FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 DANGER EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion. Notes:  You can/remove replace any I/O module without removing power. ...
  • Page 5 FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 If you are replacing an existing personality module that is already wired with an identical personality module, and if there is no fault with the terminal block, leave wiring connected to the terminal block, and disconnect the terminal block from the personality module by gently rocking the terminal block from side to side until it pops out.
  • Page 6 FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 Press the new replacement personality module into the slot until it is properly seated, then tighten the captive fastening screw. Replacing a Personality Module If you replaced an existing personality module with an identical replacement, and were able to re-use the terminal blocks, reattach the terminal block by pressing it into place;...
  • Page 7: Wiring The Module

    FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 Wiring the Module DANGER Ensure the RTU is in a non-hazardous area. Never open the enclosure in a hazardous area. DANGER EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous. Performing this operation in a hazardous area could result in an explosion.
  • Page 8 FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 Multi-Drop Mode In Multi-Drop Mode, only the HART digital signaling (FSK – Frequency Shift Keying) is present and no 4-20mA analog current signal is permitted (no AO allowed). Each device can support a maximum 4mA bias current.
  • Page 9 FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 Figure 3 shows how to wire a HART channel for devices which do not use loop power but get power from an external power supply. Figure 3. HART Wiring – External Power Supply HART Device External 24V Power Supply Analog Input Mode (HART Communication Disabled)
  • Page 10 FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 Figure 4. Methods for Connecting 4mA to 20mA Analog Inputs to 3HRT04 Channel (No HART communications) 4-20mA Analog Signal Loop Transducer Power Supply Sensor Input External Power Source 3HSTG4 Module internal ground connections (for information only;...
  • Page 11 FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 Analog Output Mode (HART Communication Disabled) If you have an unused HART channel, you can use it as a 4-20mA current sinking analog output. In FBxConnect, you must Disable the 250 Ohm Termination Resistor and set the HART Comm Mode to Disabled.
  • Page 12 FB3000 RTU HART ® I/O Module Field Installation Guide D301918X012 June 2021 Software Configuration Consult the FBxConnect online help for full details. What follows is an overview of the steps: 1. From the Configure tab in FBxConnect, click I/O Setup > HART. 2.
  • Page 14 Emerson Automation Solutions Remote Automation Solutions Emerson FZE P.O. Box 17033 © 2021 Remote Automation Solutions, a business unit of Emerson Automation Solutions. All Jebel Ali Free Zone – South 2 rights reserved. Dubai U.A.E. This publication is for informational purposes only. While every effort has been made to ensure...