3.3. Installation dimensions

Provide a service access for inspection purposes.
Do not place any wiring or illumination in the service space, as they will impede service.
3.3.1. Installation dimensions
Front view
150 or more
Strong and durable ceiling
5 to 10
Ceiling board
Cassette grille (optional parts)
Maximum height from floor to ceiling
• Standard mode: 1800 to 2700
• High Ceiling mode: 1800 to 3200
* Be sure to make the function settings with
the remote controller according to the
installed ceiling height.
Right side view
Air
Cassette grille (optional parts)

3.4. Installing the unit

Install the air conditioner in a location which can withstand a load of at least 5 times the
weight of the main unit and which will not amplify sound or vibration. If the installation
location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
• You can use the accessory template to help you install the indoor unit.
• The template helps you determine the appropriate locations for suspension bolts and
pipe openings (drain pipe and connection cable).
3.4.1. Indoor unit dimensions
Top view
En-3
400 or more
Service
space
Service access
(recommend)
20 or more
Unit: mm
Floor
Unit: mm
5 or more
Air
150 or more
WARNING
D (Cassette grille size)
C (Ceiling opening)
A (Hanger bolt pitch)
B (Indoor unit size)
Model
Dimensions
Unit: mm
Right side view
Ceiling board
3.4.2. Fix the unit
Fasten the unit securely with nuts A and B.
1000 or
(1) Hang the unit
more
Hanger bolt
Obstruction
Nut A
(locally pur-
chased)
Washer
(accessories)
If the length of hanger bolt is over 20 mm, it will be not convenient for following works:
• The opening and closing of control box cover
• Replacement of drain pump
20 or less
(2) Leveling
Base horizontal direction leveling on top of the unit.
Front view
Give a slight tilt to the drain port side. The tilt should be in the range of 0 mm to 10 mm.
Ceiling
Unit: mm
AUXV004/007/009/012
A:
752
B:
785
C:
920
D:
950
570
43
Liquid pipe port
Gas pipe port
Drain port
CAUTION
Hanger
Nut A
(locally purchased)
Nut B
(locally purchased)
Drain pump cover
Level
GOOD
10 or less
Drain port
AUXV014/018/024
1152
1190
1330
1360
Unit: mm
440
276
Cassette grille (optional parts)
Hanger bolt
Hanger
Washer
(accessories)
Unit
Nut B
(locally purchased)
Unit: mm
20 or less
Control box cover
Unit: mm
Drain port
PROHIBITED