Navien NCB700-42C Installation & Operation Manual page 63

Condensing combi boiler
Table of Contents

Advertisement

Figure 5-2. Exploded View of Gas Pipe Assembly
DANGER
See Figure 5-2. Inspect the O-ring between the venturi and
gas valve inlet adapter whenever they are disassembled.
The O-ring must be in good condition and must be installed.
Failure to comply will cause a gas leak, resulting in severe
personal injury.
62
Appendices
Packing
Gas Orifice
O-ring
(NCB700-52C)
Replace the old Orifice piece with the new part for use with LP
gas. Ensure that the Orifice is properly seated inside the port
before proceeding to the next step.
11. Replace the gas inlet pipe to its original position and use all
screws to secure all connections.
Do not overtighten as this may damage or crack
Note
the components.
12. Check the labels carefully and then connect all the wires.
13. Set the front panel DIP Switch to change the gas type.
WARNING
Ensure that you have turned off the power to the boiler
before accessing the DIP switches.
Figure 6. Set the DIP switches
Switch
Function
Setting
G20 (LNG)
Fuel
1 & 2
G30 (LPG)
Selection
G31 (LPG)
Table 1. The DIP Switch Setting by Fuel Selection
DANGER
When conversion is required, be sure to set the front
panel DIP switches according to the supply gas type.
Failure to properly set the DIP switches could cause
carbon monoxide poisoning, resulting in severe personal
injury.
1
2
O
N
1-OFF, 2-OFF
1-ON, 2-OFF
1-ON, 2-ON