For vertical ducts, the outlet must be at least 60 cm
Note
from any opening.
The dimensions (B, C, D, and E) may be reduced to
25 mm, as long as the flue terminal is extended to
clear any overhangs.

6.2 Flue Installation

WARNING
The gas removal ducts must not be in contact with
or near flammable materials and they must not pass
through any structures or walls of buildings made of
such materials.
If you replace the boiler, the old gas removal system
must be replaced by a new one.
The standard flue must be installed level. If flue
extensions are needed, they must have a 3 degree fall
back to the appliance.
The fume extraction connection depends on the type of
installation. Carefully follow the instructions given below:
Coaxial System
For coaxial flue adapter, fit the components as shown in the
figure:
28
Flue System
Adapter
6.2.1 Horizontal Coaxial Removal (Type C
Standard Removal System
B 500 or 1,000
Ø60/100 => Max. length: A = 8 m
Ø80/125 => Max. length: A = 27 m
Extended Removal System
A
Ø60/100 => Max. length: A+B-(1 x 90°elbow) = 8-1.3 = 6.7 m
Ø80/125 => Max. length: A+B-(1 x 90°elbow) = 27-2.2 = 24.8 m
)