Outdoor unit maintenance
Checklist for maintenance work
Measure
Ventilating the work location
%
Carry out repairs outdoors, or provide adequate ventilation for
the work location before interfering with the refrigerant circuit or
commencing any welding or brazing/soldering work.
The ventilation must be maintained for the entire duration of the
work. The ventilation should dilute any refrigerant that may es-
cape and should ideally discharge it into the surrounding atmos-
phere.
Checking the refrigeration system
&
Any replacement electrical components must be suitable for the
application and must correspond to the manufacturer's specifi-
cation. Only replace faulty components with genuine Viessmann
spare parts.
Carry out all component replacements in accordance with Viess-
mann guidelines. If required, consult Viessmann Technical Serv-
ice.
Perform the following checks:
The refrigerant charge must not be greater than specified in the
technical data.
If a hydraulically separated system is used, check the secondary
circuit for the presence of any refrigerant.
Labels and symbols must always be clearly visible and legible.
Replace any illegible information.
Refrigerant lines and components must be installed in such a
manner that they do not come into contact with substances that
can cause corrosion.
Exception: The refrigerant lines are made from corrosion-resist-
ant materials or are reliably protected against corrosion.
Checks on electrical components
/
Safety checks must be carried out for maintenance and repair
work on electrical components: See below.
In the event of a safety-related fault, do not connect the system
until the fault has been remedied.
If it is not possible to remove the fault immediately, provide a
suitable interim solution for the system's operation if required.
Inform the system operator.
Carry out the following safety checks:
Discharge the capacitors: Ensure no sparks are created when
discharging.
Do not position any live electrical components or cables in the
immediate vicinity of the outdoor unit when filling or extracting
refrigerant or when flushing the refrigerant circuit.
Check the earth connection.
138
(cont.)
Completed
Comments