Weil-McLain AHE Series Manual page 10

Table of Contents

Advertisement

AHE Series 4 Direct Vent Wall-Mounted Boilers — Boiler Manual
2b
Venting — side venting installation
Prepare mounting panel
6.
Determine boiler location. See Manual Section 2a
on page 8 and "Select location" on page 9.
7.
Level and tape mounting panel template to wall at
desired height between studs.
8.
To locate side wall vent:
a.
Measure from floor to center line of top
exhaust tube on large template.
b.
Subtract ¼" per foot of vent run from step "a".
Vent tubes must pitch down from boiler.
c.
Level and tape small template on side wall.
Height of top exhaust center line is distance in
step "b". Note correct "up" position for right
or left side venting.
9.
Mark location of vent/air intake opening through
template on side wall.
10. Remove template and cut opening in wall.
Outside
11. The following material is required:
a.
outside wall plate assembly (see Figure 4 on
this page and Figure 8, page 11).
b.
silicone sealant.
c.
(4) #10 x 1¼" common screws (provided) or
(4) wall anchors (not provided) for masonry
wall only.
d. screwdriver.
e.
drill with small bit (to start screws if necessary).
f.
level.
12. Using outside wall plate as template, level and locate
mounting holes.
13. Place a generous amount of silicone sealant around
wall opening. See Figure 5, right and Figure 8 on
page 11.
14. Insert outside wall plate assembly into opening and
attach to wall.
10
continued
Before installing boiler and venting,
inspect
wall
locations
obstructing piping and electrical
supply. Failure to do so will result in
severe personal injury, death or
substantial property damage.
Center of mounting panel bolt holes
must be in line with 16" studs unless
extra support board is provided.
Refer to "Wall preparation" on page
8. Failure to mount panel properly
can result in severe personal injury,
death or substantial property
damage.
Figure 4
Outside wall plate assembly
for
"UP"
88704
Figure 5
Silicone sealant
Silicone
sealant
Opening
Figure 6
Measure tube lengths
Exhaust tube
cutlines on template
Large template
88707
con't
88705
Take
measurement
from birdguard
inside both
openings
Part number 550-141-887/0800

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ahe-45Ahe-60

Table of Contents