Panasonic Aquarea WH-ADC0309J3E5 Planning And Installation Manual page 213

Air-to-water heat pumps
Hide thumbs Also See for Aquarea WH-ADC0309J3E5:
Table of Contents

Advertisement

Menus
Menu
30
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
For installer
Default Setting
Water temp. for heating ON Compensation curve
X axis: -5 °C, 15 °C
Y axis: 55 °C, 35 °C
• Temperature range: X axis: -20 °C ~ 15 °C, Y axis: See below
• Temperature range for the Y axis input:
1� WH-UD model: 20 °C ~ 60 °C
2� WH-UH model & Back up heater is enabled: 25 °C ~ 65 °C
3� WH-UH model & Back up heater is disabled: 35 °C ~ 65 °C
4� WH-UX model: 20 °C ~ 60 °C
• If 2 zone system is selected, the 4 temperature points must also be input for Zone
2�
• "Zone 1" and "Zone 2" will not appear on the display if only 1 zone system�
Water temp. for heating ON Direct
35 °C
• Min� ~ Max� range is conditional as follows:
1� WH-UD model: 20 °C ~ 60 °C
2� WH-UH model & Back up heater is enabled: 25 °C ~ 65 °C
3� WH-UH model & Back up heater is disabled: 35 °C ~ 65 °C
4� WH-UX model: 20 °C ~ 60 °C
• If 2 zone system is selected, temperature set point must input for Zone 2�
• "Zone 1" and "Zone 2" will not appear on the display if only 1 zone system�
Outdoor temp. for heating OFF
24 °C
T for heating ON
5 °C
Heater ON/OFF
Heater ON/OFF Outdoor temp. for heater ON
0 °C
Setting Options / Display
Input the 4
temperature points
(2 on horizontal X
axis, 2 on vertical Y
axis)�
Temperature for
heating ON
Temperature for
heating OFF
Set T for heating
ON�
* This setting will not
available to set when
pump flowrate set to
Max� duty�
Temperature for
heater ON
Appendix
8
213