Download Print this page

Viking MICROMATIC VK106 Technical Data Manual page 3

Standard response vertical sidewall sprinkler

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Base Part
Maximum
SIN
Number
Pressure
1
12996
VK106
175 psi
4
12991
VK106
175 psi
4
10226
VK106
175 psi
4
17496
VK106
175 psi
4
10186
VK106
175 psi
4
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F
(93 °C), and 286 °F (141 °C)
B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and
286 °F (141 °C)
Base part number shown. For complete part number, refer to Viking's current price schedule.
1
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
2
This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
3
Viking vertical sidewall sprinklers may be installed pendent or upright.
4
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40286
6
FM Approval Requirements:
Vertical Sidewall Sprinkler VK106 is FM Approved as a standard response sidewall Non-Storage sprinkler, as indicated in the FM Approval Guide.
For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including 2-0) and Technical
Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum
water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below
the ceiling.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza-
tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F_052414
18.10.11
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Approval Chart
Micromatic
Standard Response Vertical Sidewall Sprinkler VK106
®
Nominal
Thread Size
K-Factor
NPT
BSP
U.S.
metric
1/2"
15 mm
5.6
80.6
--
15 mm
5.6
80.6
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
1/2"
15 mm
5.6
80.6
1/2"
15 mm
5.6
80.6
--
15 mm
5.6
80.6
DESIGN CRITERIA
(Also refer to the Approval Chart above.)
Rev 17.1.P65
Overall Length
Inches
mm
cULus
2
Standard Orifice
2-1/4
58
--
2-1/4
58
--
2-1/4
58
--
2-1/4
58
--
2-1/4
58
--
Approved Finishes
X - Installed with standard surface-mounted escutch-
1 - Brass and Chrome
Footnotes
MICROMATIC
STANDARD
®
RESPONSE VERTICAL
SIDEWALL SPRINKLER
VK106 (K5.6)
Listings and Approvals
(Refer also to Design Criteria below.)
FM
VdS
LPCB
4
A1X
A1
--
A1X
--
--
B1X
A1
--
B1X
A1
--
B1X
A1
--
Approved Escutcheons
eons
Replaces Form No. F_052414 Rev 17.1
(Added P65 Warning.)
Page 3 of 3
3
--
--
--
--
A1
--
A1
--
A1
--

Advertisement

loading

This manual is also suitable for:

129964129914102264174964101864