Safety Information - Read First - Honeywell BW MaxXT II User Manual

1, 2, 3, and 4 gas detector
Hide thumbs Also See for BW MaxXT II:
Table of Contents

Advertisement

Safety Information - Read First

Use the detector only as specified in this technical reference guide, otherwise the protection
provided by the detector may be impaired.
Read the See "Cautions" below for more information. on the following pages before using the
detector.
This instrument contains a lithium polymer battery. Dispose of lithium cells immediately. Do
not disassemble and do not dispose of in fire. Do not mix with the solid waste stream. Spent
batteries must be
disposed of by a qualified recycler or hazardous materials handler.
Cautions
Warning: Substitution of components may impair Intrinsic Safety.
l
Caution: For safety reasons, this equipment must be operated and serviced by qualified
l
personnel only. Read and understand the technical reference guide completely before
operating or servicing.
Do not use the detector if it is damaged. Inspect the detector before using. Look for
l
cracks and/or missing parts.
If the detector is damaged or parts are missing, contact Honeywell BW™ MaxXT II
l
immediately.
Use only sensor(s) that are specifically designed for the MaxXT II model. Refer to
l
Replacement Parts and Accessories.
Calibrate the detector before first-time use and then on a regular schedule, depending on
l
use and sensor exposure to poisons and contaminants. Sensors must be calibrated
regularly and at least once every 180 days (6 months).
Honeywell recommends to bump test the sensors, before each day's use, to confirm their
l
ability to respond to gas by exposing the detector to a gas concentration that exceeds the
alarm setpoints. Manually verify that the audible and visual alarms are activated. Calibrate
if the readings are not within the specified limits.
Protect the combustible sensor from exposure to lead compounds, silicones, and
l
chlorinated hydrocarbons. Although certain organic vapors (such as leaded gasoline and
halogenated hydrocarbons) may temporarily inhibit sensor performance, in most cases,
the sensor will recover after calibration.
Honeywell recommends the combustible sensor be checked with a known concentration
l
of calibration gas after any known exposure to catalyst contaminants/poisons (sulfur
compounds, silicon vapors, halogenated compounds, etc).
BW MaxXT II
WARNING
7
User Manual