Technical Service Data - Friedrich H)A09K25L Service Manual

Single package vertical air conditioning system r410a models vert-i-pak a series
Table of Contents

Advertisement

ELECTRICAL
RATINGS
SERVICE DATA
Cooling¹
Voltage
Amps
VEA09K**RTL
230/208
4.2
VEA12K**RTL
230/208
5.2
VEA18K**RTL
230/208
8.1
VEA24K**RTL
230/208
10.0
VHA09K**RTL
230/208
4.1
VHA12K**RTL
230/208
5.3
VHA18K**RTL
230/208
8.2
VHA24K**RTL
230/208
10.6
¹Test Conditions: 80º F, Room Air Temperature with 50% Relative Humidity, and 95º F, Outdoor Air Temperature with 40% Relative Humidity
**Denotes Heater KW - Numbers Vary

TeChNICAL seRVICe DATA

TECHNICAL SERVICE DATA
INDOOR COIL
TEMPERATURE
OUTDOOR COIL
º F
TEMPERATURE
º F
Temperature
Supply Air
Drop
58
22
118
57
23
116
55
25
127
55
25
125
57
23
117
55
25
119
51
29
129
51
29
128
Discharge Line
Suction Line
Temperature
Temperature
Super Heat
º F
º F
156
66
158
59
12
180
60
12
170
61
10
155
62
12
165
65
15
190
60
14
174
60
12
OPERATING
PRESSURES
Sub-Cooling
Suction
Discharge
9
24
151
389
17
141
396
28
135
455
34
135
440
20
155
405
23
145
450
35
133
465
32
140
480
Refrigerant
Charge
R-410A - Oz.
33.5
32.0
48.0
65.0
39.0
42.0
45.0
74.0
41

Advertisement

Table of Contents
loading

Table of Contents