2.1 Prestart Checklist

To ensure continued satisfactory operation, perform the
following checks or inspections before or at each
startup, as designated, and at the intervals specified in
the service schedule. In addition, some checks require
verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner
element to prevent unfiltered air from entering the
engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer's instructions regarding
battery care and maintenance.
Exhaust System.
Check for exhaust leaks and
blockages. Check the muffler and piping condition and
check for tight exhaust system connections.
Inspect the exhaust system components (exhaust
manifold, exhaust line, flexible exhaust, clamps,
silencer, and outlet pipe) for cracks, leaks, and
corrosion.
D
Check for corroded or broken metal parts and replace
them as needed.
D
Check that the exhaust outlet is unobstructed.
D
Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components.
Carbon and soot residue indicates an exhaust leak.
Seal leaks as needed.
Oil Level. Maintain the oil level at or near, not over, the
full mark on the dipstick.
Operating Area. Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.
Control or Indicator
Item
Runtime hours
LED display
Crank indication
Fault codes
Generator set master
Three-position
switch
switch
Figure 2-2 DC 2200 Controls and Indicators
TP-6398 4/07

2.2 Generator Set Operation

2.2.1
Figure 2-1 illustrates the front panel of the Digital
Control (DC 2200) generator set controller.
Figure 2-2 describes the controls and indicators located
on the DC 2200. The LED display indicates generator
set status as shown in Figure 2-2.
The LED display is activated:
D
When the generator set master switch is moved to the
RUN position.
D
When a remote start command is received and the
generator set master switch is in the AUTO position
The display turns off 48 hours after the generator set
shuts down.
1. LED display
2. Generator set master switch
Figure 2-1 DC 2200 Front Panel
Description
Displays total generator set runtime hours while the generator set is running and when no
other codes are displayed.
Displays CC_1, CC_2, or CC_3 to indicate the first, second, or third attempt to start the
engine. The last digit flashes during the crank cycle rest periods.
Flashes a 2- or 3-letter fault code to indicate various fault conditions. See Section 2.4.
Switch functions as the generator set operation and controller reset switch.