Fan Performance, 48Tf012 — Vertical Discharge Units (Si) - Carrier 48TFD008-014 Installation And Service Instructions Manual

Single-package rooftop heating/cooling units 50 hz
Table of Contents

Advertisement

Table 13 — Fan Performance, 48TF012 — Vertical Discharge Units (SI)
AIRFLOW
50
(L/s)
R/s
1500
9.8
1550
10.0
1600
10.3
1650
10.6
1700
10.9
1750
11.1
1800
11.4
11.7
1850
1900
12.0
1950
12.2
2000
12.5
2050
12.8
2100
13.1
2150
13.3
2200
13.6
2250
13.9
14.2
2300
2400
14.5
2450
14.8
AIRFLOW
300
(L/s)
R/s
1500
14.6
1550
14.8
1600
15.0
1650
15.1
1700
15.3
1750
15.5
1800
15.8
1850
16.0
1900
16.2
1950
16.4
2000
16.6
2050
16.8
2100
17.0
2150
17.2
2200
2250
2300
2400
2450
LEGEND
BkW — Fan Input kW x Motor Efficiency
R/s
— Revolutions Per Second of Blower Wheel
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 5.)
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
EXTERNAL STATIC PRESSURE (Pa)
100
BkW
R/s
BkW
0.55
10.9
0.67
0.60
11.2
0.74
0.66
11.4
0.80
0.72
11.7
0.86
0.78
12.0
0.93
0.86
12.2
1.00
0.93
12.5
1.08
1.00
12.7
1.15
1.08
12.9
1.23
1.16
13.2
1.31
1.25
13.4
1.40
1.34
13.7
1.50
1.44
13.9
1.60
1.53
14.2
1.71
1.64
14.5
1.82
1.75
14.7
1.94
1.86
15.0
2.06
1.98
15.3
2.19
2.10
15.6
2.32
EXTERNAL STATIC PRESSURE (Pa)
350
BkW
R/s
BkW
1.15
15.3
1.26
1.23
15.5
1.35
1.30
15.7
1.44
1.39
15.9
1.52
1.47
16.1
1.61
1.56
16.3
1.70
1.66
16.4
1.80
1.75
16.6
1.90
1.86
16.9
2.01
1.96
17.1
2.12
2.07
17.3
2.24
2.18
17.5
2.36
2.30
2.41
150
R/s
BkW
R/s
12.0
0.79
12.9
12.2
0.86
13.1
12.4
0.92
13.3
12.6
0.98
13.6
12.8
1.06
13.7
13.1
1.14
14.0
13.3
1.22
14.2
13.6
1.31
14.4
13.8
1.40
14.6
14.1
1.49
14.8
14.3
1.59
15.1
14.6
1.69
15.3
14.9
1.80
15.6
15.1
1.91
15.8
15.3
2.02
16.1
15.6
2.13
16.3
15.8
2.25
16.6
16.1
2.38
400
R/s
BkW
R/s
16.1
1.38
16.9
16.2
1.47
17.1
16.4
1.55
17.1
16.6
1.65
17.3
16.8
1.74
17.4
17.0
1.85
17.6
17.2
1.95
17.8
17.3
2.05
18.0
17.5
2.16
18.2
17.7
2.26
18.4
17.9
2.39
5. Standard drive range is 9.5 to 13.0 r/s. All other speeds require
a field-supplied drive.
6. Maximum continuous BkW is 1.79. Extensive motor and electri-
cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
23
200
250
BkW
R/s
BkW
0.92
13.8
1.04
0.98
13.9
1.11
1.05
14.2
1.18
1.12
14.4
1.25
1.20
14.6
1.34
1.28
14.8
1.42
1.36
15.0
1.52
1.44
15.2
1.60
1.53
15.4
1.70
1.63
15.6
1.79
1.74
15.9
1.90
1.85
16.1
2.00
1.97
16.3
2.12
2.09
16.5
2.24
2.21
16.8
2.37
2.34
2.47
450
500
BkW
R/s
BkW
1.45
17.7
1.68
1.60
17.8
1.81
1.68
17.9
1.86
1.77
18.0
1.91
1.88
18.1
2.00
1.98
18.2
2.11
2.09
18.4
2.22
2.20
18.6
2.34
2.31
2.43