Siemens SITRANS FCT030 Quick Start Manual

Siemens SITRANS FCT030 Quick Start Manual

Hide thumbs Also See for SITRANS FCT030:

Advertisement

Quick Links

SITRANS F
Coriolis Flowmeters
SITRANS FCT030 transmitter
Quick Start
Before installing, including in hazardous areas, refer to the Operating Instructions on the internet or on the SITRANS F
literature CD-ROM. They contain detailed safety regulations, information and specifications which must be observed when
installing. Documentation and approvals can be found on the internet:
Flowdocumentation (http://www.siemens.com/flowdocumentation)
CAUTION
Correct, reliable operation of the device requires proper transport, storage, positioning and assembly. The device must be
carefully operated and maintained. Only qualified personnel should install or operate this device.
Items supplied
Compact system
● SITRANS FC430 sensor and compact mounted
transmitter
● Packet of cable glands
● Quick Start guide
● CD containing software, certificates and device manuals
Remote system
With M12 connection
● SITRANS FCS400 sensor
● SITRANS FCT030 transmitter with M12 socket assembled
● Mounting bracket and cushion pad
● Sensor cable with M12 connector
● Packet of cable glands
● Quick Start guide
● CD containing software, certificates and device manuals
© Siemens, All rights reserved Ⓟ 2012
A5E03922778-01, 03/2012
*A5E03922778*
1

Advertisement

loading

Summary of Contents for Siemens SITRANS FCT030

  • Page 1 ● CD containing software, certificates and device manuals Remote system With M12 connection ● SITRANS FCS400 sensor ● SITRANS FCT030 transmitter with M12 socket assembled ● Mounting bracket and cushion pad ● Sensor cable with M12 connector ● Packet of cable glands ●...
  • Page 2: Remote Mounting

    With terminal housing ● SITRANS FCS400 sensor ● SITRANS FCT030 transmitter with terminal housing assembled ● Mounting bracket and cushion pad ● Sensor cable ● Packet of cable glands ● Quick Start guide ● CD containing software, certificates and device manuals Note Scope of delivery may vary, depending on version and add-ons.
  • Page 3 2. Loosen lock screw at transmitter pedestal using 5 mm Allen key. 3. Carefully rotate transmitter into desired position. 4. Firmly tighten lock screw (torque: 10 Nm). 5. Replace cap onto lock screw (torque: 10 Nm). SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 4 1. Remove blind plugs where required and mount cable glands. ① Input/output connection (channels 2 to 4) ② Power supply connection ③ Current output/HART connection (channel 1) 2. Remove lid lock screw for terminal connections lid. 3. Remove lid for terminal connections. SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 5 Signal output channel 2 negative ⑪ IO3+ Input/output channel 3 positive ⑫ Input/output channel 3 common ⑬ IO3- Input/output channel 3 negative ⑭ IO4+ Input/output channel 4 positive ⑮ Input/output channel 4 common ⑯ IO4- Input/output channel 4 negative SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 6 3. Push cable through open gland and cable path. 4. Restore ferrule and tighten cap to lightly hold cable in place. 5. Connect ground to terminal and power to terminals L/+ and N/- using wiring tool in the manner shown below at right. SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 7 3. Restore ferrule and tighten cap to lightly hold cable in place. 4. Signal cable screen is folded back over outer sheath and grounded beneath cable clamp. 5. Connect wires to terminals using wiring tool. SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 8 3. Restore ferrule and tighten cap to lightly hold cable in place. 4. Signal cable screen is folded back over outer sheath and grounded beneath cable clamp. 5. Connect wires to terminals using wiring tool. SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 9 Signal input Start dosing, stop dosing, reset tot. Active 1, reset tot. 2, IOXp- reset tot. 3, reset IOXC all totalizers, start zero point IOXa+ adjustment, pause/resume dosing, force output, or freeze output SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 10 6. Reinstate and tighten lid lock screw where supplied. 7. Ensure that moisture does not penetrate to inside of electronics housing by creating a drip loop (bend cables downward) immediately before cable glands. SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 11 The navigation view shows the menus and parameters. The navigation view is used to navigate to the menus and parameters in the device. ● Parameter view The parameter view can be entered form the navigation view. The parameter view is used to view and edit the parameters. SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 12 No functionality No functionality No functionality The following graphic shows an example of how to navigate between measurement views and alarm views with measurement views 1, 3, and 4 as well as alarm view 5 enabled. SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 13 If a parameter is selected in the navigation view then enter the parameter view Editing the parameters When this symbol is shown in the graphics, the four buttons on the LUI are used for changing the parameters as described below. SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 14 Menu item 1.6: Fluid temperature Fraction Menu item 1.7: Fraction Totalizer 1 Menu item 1.8: Totalizer 1 Totalizer 2 Menu item 1.9: Totalizer 2 1.10 Totalizer 3 Menu item 1.10: Totalizer 3 Start Zero Point Adj. 1.11 SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 15 Polling Address (SW) Communication Polling Address (HW) HART Device Type HART Revision Mapping of Variables Menu item 4.6: Mapping of Variables HART Units Menu item 4.7: HART Units Security Access Management Menu item 5.1: Access Management Language SITRANS FCT030 transmitter A5E03922778-01, 03/2012...
  • Page 16 Responsibility for suitability and intended use of this instrument rests solely with the user. Copyright © Siemens AG 03.2012 All Rights Reserved. Technical data subject to change without prior notice. SITRANS FCT030 transmitter (CN) SITRANS FCT030 transmitter...
  • Page 17 ● 电缆接头包 ● 快速入门指南 ● 包含软件、证书及设备手册的 CD 远程型系统 采用 M12 连接方式 ● SITRANS FCS400 传感器 ● 装有 M12 插座的 SITRANS FCT030 变送器 ● 安装支架和垫片 ● 带有 M12 连接器的传感器电缆 ● 电缆接头包 ● 快速入门指南 ● 包含软件、证书及设备手册的 CD © Siemens, 保留所有权利 Ⓟ 2012...
  • Page 18 带端子外壳 ● SITRANS FCS400 传感器 ● 装有端子外壳的 SITRANS FCT030 变送器 ● 安装支架和垫片 ● 传感器电缆 ● 电缆接头包 ● 快速入门指南 ● 包含软件、证书及设备手册的 CD 说明 交付内容根据版本及附加件而有所变化。产品包装内的内容列表会列出所有随附零件。 说明 传感器安装 FCS400 传感器的安装在 SITRANS FCS400 快速入门 (A5E03649755) 中有描述。 远程安装 墙式安装 1. 借助安装支架打孔。 2. 将带有垫片的安装支架固定到墙上(扭矩为 10 Nm)。...
  • Page 19 安装变送器 1. 从安装支架上卸下螺丝。 2. 在安装支架上安装变送器,注意接触面上的凹槽正确啮合。 3. 拧紧安装支架上的螺丝(扭矩:25 Nm)。 转动变送器 在远程配置中,变送器可水平或垂直转动。在紧凑配置中,变送器只能水平转动。 水平旋转 1. 从锁紧螺丝上拧下螺丝帽。 2. 使用 5 mm 内六角扳手松开变送器基座上的锁紧螺丝。 3. 小心地将变送器旋转至所需位置。 4. 拧紧锁紧螺丝(扭矩:10 Nm)。 5. 将螺丝帽放回锁紧螺丝(扭矩:10 Nm)。 垂直旋转 1. 转动三圈安装支架末端的固定帽以将其松开。 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 20 2. 小心地将变送器松开并将其旋转至所需位置(15° 步距)。 3. 拧紧固定帽(扭矩:25 Nm)。 连接 警告 只要设备通电,就只有合格人员才能在传感器连接区域上打开外壳盖。 在取下端子盖前,必须从所有电极处断开辅助电源。 安装后,必须再次拧回端子盖。 1. 如果需要,取下空插头,然后安装电缆接头。 ① 输入/输出连接(通道 2 到 4) ② 电源连接 ③ 电流输出/HART 连接(通道 1) 2. 取下端子连接盖上的机盖锁紧螺丝。 3. 取下端子连接盖。 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 21 信号输出通道 2 公共 ⑩ IO2- 信号输出通道 2 反向 ⑪ IO3+ 输入/输出通道 3 正向 ⑫ 输入/输出通道 3 公共 ⑬ IO3- 输入/输出通道 3 反向 ⑭ IO4+ 输入/输出通道 4 正向 ⑮ 输入/输出通道 4 公共 ⑯ IO4- 输入/输出通道 4 反向 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 22 接线工具 使用接线工具连接电缆。 接线工具位于应用端子区域。 接线工具位置 1. 将接线工具的钩子插入接收器槽内。 2. 将接线工具楔压入顶槽以展开夹板。 3. 插入电线。 4. 松开接线工具。 电源 1. 翻开电源端子保护盖。 2. 从电缆接头取下盖帽和套圈,然后滑到电缆上。 3. 将电缆穿过打开的接头和电缆路径。 4. 将套圈放回原位,然后拧紧盖帽,轻轻地将电缆固定到位。 5. 按照下图右侧所示,使用接线工具将地线连接到端子 ,并将电源连接到端子 L/+ 和 N/-。 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 23 电源:100 到 240 V AC + 10/- 15 %,47 到 63 Hz 电源:24 到 90 V DC + 20/- 20 % 6. 用夹条固定电缆。 7. 关闭并闭锁电源端子保护盖。 8. 拧紧电缆接头。 电流输出/HART(通道 1) 1. 从电缆接头取下盖帽和套圈,然后滑到电缆上。 2. 将电缆穿过打开的接头和电缆路径。 3. 将套圈放回原位,然后拧紧盖帽,轻轻地将电缆固定到位。 4. 将信号电缆屏蔽向后折叠到外护套上并在电缆夹下方接地。 5. 使用接线工具将电线连接到端子。 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 24 被动电流输出 ⑤ ⑥ ④ ⑤ 主动电流输出 被动电流输出 6. 拧紧电缆接头。 说明 在订货时预选主动或被动电流输出。 说明 负载 电流输出(通道 1):< 500 Ω (HART ≥ 230 Ω) 输入和输出(通道 2 到 4) 1. 从电缆接头取下盖帽和套圈,然后滑到电缆上。 2. 将电缆穿过打开的接头和电缆路径。 3. 将套圈放回原位,然后拧紧盖帽,轻轻地将电缆固定到位。 4. 将信号电缆屏蔽向后折叠到外护套上并在电缆夹下方接地。 5. 使用接线工具将电线连接到端子。 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 25 IOXC 级给料或二级给料 IOXa+ IOXa+ 信号输入 开始给料、停止给 料、复位累加器 主动 1、复位累加器 IOXp- 2、复位累加器 IOXC 3、复位所有累加 器、开始零点调 IOXa+ 整、暂停/继续给 料、强制输出或冻 结输出 信号输入 开始给料、停止给 料、复位累加器 被动 1、复位累加器 IOXp- IOXp- 2、复位累加器 IOXC IOXC 3、复位所有累加 器、开始零点调 IOXa+ IOXa+ 整、暂停/继续给 料、强制输出或冻 结输出 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 26 信号输出: < 500 Ω 继电器输出: 30 V AC/DC,100 mA 连接检查 1. 通过拉紧来检查各条电线的安装。 2. 拧紧电缆接头,然后将堵塞插头插入未使用的电缆入口。 3. 从机盖上取下 O 形环。 4. 将机盖按原状恢复并拧入螺丝,直到机械固定为止。将机盖倒转一圈。 5. 通过拉动 O 形环将其盖在机盖上来安装 O 形环,然后拧紧机盖直到感觉 O 形环两侧都有摩擦为止。将机盖转动四分之一 圈,以密封 O 形环。 6. 复原并拧紧随附的机盖锁紧螺丝。 7. 紧邻电缆接头之前创建一个滴水圈(使电缆向下弯曲),以确保水分不会渗入到电子设备机壳内部。 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 27 操作无需打开设备。这意味着可始终保证 IP67 的高防护等级和在危险场所使用的安全性。 使用菜单结构 有三种视图类型: ● 操作视图 操作员视图最多可显示六个操作视图。 操作视图完全可组态,以显示不同操作视图类型的不同过程值。 根据操作视图类 型配置,视图为测量视图或报警视图。 – 测量视图: 显示测量值。 – 报警视图: 在列表中显示活动报警。 ● 导航视图 导航视图显示菜单和参数。 导航视图用于在设备中导航至菜单和参数。 ● 参数视图 参数视图可从导航视图进入。 参数视图用于查看和编辑参数。 导航操作视图 使用如下控制按钮浏览操作视图和菜单项: 表格 5-1 测量视图 按键 功能 无功能 转到操作视图中的上一菜单 转到操作视图中的下一菜单 进入导航视图 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 28 无功能 转到操作视图中的上一菜单 转到操作视图中的下一菜单 进入报警视图级别 2 表格 5-3 报警视图级别 2 按键 功能 进入报警视图级别 1 在列表中选择上方项目;按住该按键可加速向上滚动选择列表 在列表中选择下方项目;按住该按键可加速向下滚动选择列表 进入报警视图级别 3 表格 5-4 报警视图级别 3 按键 功能 进入报警视图级别 2 无功能 无功能 无功能 *下图显示了在启用测量视图 1、3 和 4 以及报警视图 5 的情况下如何在测量视图和报警视图之间导航的示例。 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 29 报警视图 - 级别 2 ⑦ 报警视图 - 级别 3 浏览导航视图 使用如下控制按钮浏览导航视图和菜单项: 表格 5-5 导航视图 按键 功能 进入下一更高级别的导航视图(例如,从级别 2 到级别 1)。 如果已位于导航视图级别 1,则进入操作视图 在列表中选择上方项目;按住该按键可加速向上滚动选择列表。 如果在选中顶部项目时按下该键,底部项 目将会突出显示 在列表中选择下方项目;按住该按键可加速向下滚动选择列表。 如果在选中底部项目时按下该键,顶部项 目将会突出显示 进入下一更低级别的导航视图(例如,从级别 1 到级别 2)。 如果在导航视图中选择参数,则进入参数视图 编辑参数 图形中显示此符号 时,菜单界面上的四个按钮用于更改参数,如下所述。 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 30 菜单项 1.4: 体积流量 密度 菜单项 1.5: 密度 流体温度 菜单项 1.6: 流体温度 分数 菜单项 1.7: 分数 累加器 1 菜单项 1.8: 累加器 1 累加器 2 菜单项 1.9: 累加器 2 1.10 累加器 3 菜单项 1.10: 累加器 3 开始零点调整 1.11 SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 31 菜单项 3.7: 模拟 自测 菜单项 3.8: 自测 给料测试 菜单项 3.9: 给料测试 轮询地址 (SW) 通信 轮询地址 (HW) 标签 HART 设备类型 HART 版本 变量绘制 菜单项 4.6: 变量绘制 HART 单位 菜单项 4.7: HART 单位 安全 访问管理 菜单项 5.1: 访问管理 Language SITRANS FCT030 变送器 A5E03922778-01, 03/2012...
  • Page 32 Siemens A/S Flow Instruments 我们已经查阅了此手册的内容以保证与所描述硬件的一致性。由于无法完全排除未来的变化情况,因此我们 DK-6430 Nordborg 无法保证绝对一致性。尽管如此,此手册中的信息会被定期审查。以后版本中将包括所有必需的修改内容。 使用者须对仪表的配套使用和用途负全责。 www.siemens.com/flow 版权:西门子股份有限公司 03.2012 版权所有。保留修改权 SITRANS FCT030 变送器 (CN) SITRANS FCT030 变送器 A5E03922778, 03/2012...