Carrier REFRIGERANT R-410A Installation And Service Instructions Manual page 28

Packaged air-handling units 60 hz with puron (r-410a) refrigerant sizes 25, 28, 30
Hide thumbs Also See for REFRIGERANT R-410A:
Table of Contents

Advertisement

Table 9C — High-Static Drive Data, 60 Hz — English
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (in.)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. — Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed (rpm)
1
Change per
/
Turn of
2
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (in.)
It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 1200 rpm.
Table 9D — Standard Drive Data, 60 Hz — SI
UNIT
MOTOR DRIVE
Motor Pulley Pitch Diameter (mm)
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm)
Pulley Bore (mm)
Belt No. — Section
Belt Pitch (mm)
FAN SPEEDS (r/s)
Factory Setting
Range
Max Allowable Speed (r/s)
1
Change per
/
Turn of
2
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER DISTANCE (mm)
Four belts shipped with unit. Use correct set of 2 belts sized according to the pully setting.
40RUA*25
40RUA*28
40RUS*25
40RUS*28
4.3-5.3
4.3-5.3
3.0
3.0
7.4
8.6
7
15
1
/
1
/
16
16
2—B
2—B
36.8
378
1118
1024
1014-
873-
1200
1075
1200
1100
19.4
16.7
6
6
8.16-
6.67-
10.02
9.43
40RUA*25
40RUA*28
40RUS*25
40RUS*28
94.0-
109.2-
119.4
134.6
3.0
3.0
239
279
36.5
49.2
2—B
2—B
(2) 1987
1062
(2) 1113
12.9
12.5
11.3-14.4
11.4-14.0
20.0
18.3
0.255
0.218
6
6
232-279
169-240
28
40RUA*30
40RUS*30
4.3-5.3
3.0
8.6
15
1
/
16
2—B
37.8
1024
873-
1075
1100
16.7
6
6.67-
9.43
40RUA*30
40RUS*30
109.2-
134.6
3.0
279
49.2
2—B
(2) 1987
(2) 1113
12.5
11.2-13.9
18.3
0.218
6
169-240