Table 5: Min. Starting Ambient Temperatures; Table 6: Control Settings And Time Delays - Trane CSRA010FAF0 Installation Operation & Maintenance

10 and 15 ton air-cooled cold generators
Table of Contents

Advertisement

Table 5: Minimum Starting Ambient Temperatures for CGA Units
Low Ambient Units
No HGBP
10 Ton
0
15 Ton
0
Notes:
1. Minimum starting ambients in degrees F, based on unit at minimum
step of unloading and 5 m.p.h. wind across condenser.
Table 6: Control Settings and Time Delays for CGA Units
Control
Description
High Pressure Cutout
Low Pressure Cutout
Std. Units
Low Temperature Cutout
Std. Units
Control
Description
Anti-short Cycle Timer
Delay Between
Compressors
Low Ambient Start Timer
CSRA-SVX01A-EN
Installation
Electrical
Designation
HPC01, HPC02
400 ± 10 psig
LPC01, LPC02
LTC
Electrical
Designation
ASCT1, ASCT2
Normally-open
timed to close
DBC
Normally-open
timed to close
LAST1, LAST2
Normally-Closed
timed to open
Contacts
Contacts Close
Open
250 ± 15 psig
38.5 ± 1 psig
44.5 ± 2 psig
36 ± 3 F
Manual Reset
Contacts
Time Delay
Status
Duration
3 Minutes
30 Seconds
4 Minutes
(Reset)
25

Advertisement

Table of Contents