Table 3 - - Electrical Data - - Units With Optional Powered Convenience Outlet (cont)
VOLTAGE
NOMINAL
RANGE
UNIT
POWER SUPPLY
50PG
Min
Max
Volts-Ph-Hz
460-3-60
414
506
05
(cont)
575-3-60
518
633
06
208/230-1-60
187
253
LEGEND
FLA
--- Full Load Amps
HACR --- Heating, Air Conditioning and Refrigeration
IFM
--- Indoor (Evaporator) Fan Motor
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC
--- National Electrical Code
OFM
--- Outdoor (Condenser) Fan Motor
RLA
--- Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power
distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
{ Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
COMPRESSOR
OFM
POWER
EXHAUST
FLA
RLA
LRA
FLA
7.1
46
0.5
0.6
5.1
34
0.5
1.4
26.9
145
1.5
1.4
max voltage deviation from average voltage
average voltage
ELECTRIC HEAT
IFM
IFM
FLA
TYPE
FLA
5.8
8.7
Low
2.1
11.5
17.3
23.1
5.8
8.7
High
2.6
11.5
17.3
23.1
5.8
8.7
Low
2.1
11.5
17.3
23.1
5.8
8.7
High
2.6
11.5
17.3
23.1
9.2
Low
2.1
13.9
18.5
9.2
High
2.0
13.9
18.5
9.2
Low
2.1
13.9
18.5
9.2
High
2.0
13.9
18.5
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
Low
4.9
52.0/ 60.0
69.3/ 80.0
86.7/100.0
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
High
7.0
52.0/ 60.0
69.3/ 80.0
86.7/100.0
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
Low
4.9
52.0/ 60.0
69.3/ 80.0
86.7/100.0
17.3/ 20.0
26.0/ 30.0
34.7/ 40.0
High
7.0
52.0/ 60.0
69.3/ 80.0
86.7/100.0
Example: Supply voltage is 230 ---3 ---60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
19
DISCONNECT
POWER SUPPLY
Nominal
MCA
MOCP†
FLA
kW*
13.7
15
14
5.0
13.7
15
14
7.5
16.3
20
15
10.0
19.8
20
18
15.0
27.0
30
25
20.0
34.3
35
32
14.2
15
14
5.0
14.2
15
14
7.5
16.9
20
16
10.0
20.4
25
19
15.0
27.6
30
25
20.0
34.9
35
32
14.3
15
14
5.0
14.3
15
14
7.5
17.0
20
16
10.0
20.5
25
19
15.0
27.8
30
26
20.0
35.0
40
32
14.8
15
15
5.0
14.8
15
15
7.5
17.6
20
16
10.0
21.1
25
19
15.0
28.4
30
26
20.0
35.6
40
33
10.7
15
11
10.0
16.3
20
15
15.0
22.1
25
20
20.0
27.9
30
26
10.6
15
11
10.0
16.1
20
15
15.0
22.0
25
20
20.0
27.8
30
26
12.1
15
12
10.0
18.0
20
17
15.0
23.9
25
22
20.0
29.6
30
27
12.0
15
12
10.0
17.9
20
16
15.0
23.8
25
22
20.0
29.5
30
27
44.8/ 44.8
50/ 50
44/44
3.8/ 5.0
44.8/ 44.8
50/ 50
44/44
5.6/ 7.5
44.8/ 49.6
50/ 50
44/46
7.5/10.0
55.5/ 62.1
60/ 70
51/57
11.3/15.0
77.1/ 87.1
80/ 90
71/80
15.0/20.0
98.8/112.1
100/125
91/103 165/165
18.8/25.0
120.5/137.1
125/150
111/126 165/165
46.9/ 46.9
50/ 50
46/ 46 190/190
3.8/ 5.0
46.9/ 46.9
50/ 50
46/ 46 190/190
5.6/ 7.5
47.3/ 52.3
50/ 60
46/ 48 190/190
7.5/10.0
58.1/ 64.8
60/ 70
53/ 60 190/190
11.3/15.0
79.8/ 89.8
80/ 90
73/ 83 190/190
15.0/20.0
101.4/114.8
110/125
93/106 190/190
18.8/25.0
123.1/139.8
125/150
113/129 190/190
46.2/ 46.2
50/ 50
45/ 45 167/167
3.8/ 5.0
46.2/ 46.2
50/ 50
45/ 45 167/167
5.6/ 7.5
46.4/ 51.4
50/ 60
45/ 47 167/167
7.5/10.0
57.3/ 63.9
60/ 70
53/ 59 167/167
11.3/15.0
78.9/ 88.9
80/ 90
73/ 82 167/167
15.0/20.0
100.5/113.9
110/125
92/105 167/167
18.8/25.0
122.3/138.9
125/150
112/128 167/167
48.3/ 48.3
50/ 50
48/ 48 192/192
3.8/ 5.0
48.3/ 48.3
50/ 50
48/ 48 192/192
5.6/ 7.5
49.0/ 54.0
50/ 60
48/ 50 192/192
7.5/10.0
59.9/ 66.5
60/ 70
55/ 61 192/192
11.3/15.0
81.5/ 91.5
90/100
75/ 84 192/192
15.0/20.0
103.1/116.5
110/125
95/107 192/192
18.8/25.0
124.9/141.5
125/150
115/130 192/192
224 + 231 + 226
3
681
=
3
=
227
4
227
SIZE
LRA
55
55
55
55
55
55
64
64
64
64
64
64
56
56
56
56
56
56
65
65
65
65
65
65
42
42
42
42
48
48
48
48
44
44
44
44
50
50
50
50
165/165
165/165
165/165
165/165
165/165

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50pg0350pg0450pg0550pg0650pg07

Table of Contents