Honeywell Notifier NFS2-3030 Product Installation Document page 12

High-speed network communications module
Hide thumbs Also See for Notifier NFS2-3030:

Advertisement

6.3 Interconnecting Modules
NOTE: BroadR-Reach references HS-NCM-W-2 connections and VDSL references HS-NCM-W connections
6.3.1 Replacing the HS-NCM-W with the HS-NCM-W-2
When connecting the HS-NCM-W to a HS-NCM-W-2 you must use an RJ45 Ethernet cable. Refer to Figure 12, "Replacing a HS-NCM-W with a HS-
NCM-W-2"
Board 1
Legend
BroadR-Reach
VDSL
Ethernet
From previous node
Port A
Board 2
NOTE: When replacing a HS-NCM-W with a HS-NCM-W-2 the immediate adjacent nodes must also be replaced
Programming for Replacing a HS-NCM-W-2 into an existing system
Refer to Figure 12, "Replacing a HS-NCM-W with a HS-NCM-W-2"
To establish a link, each board should be programed individually from its local panel as follows:
Board 1: Check "Ethernet Enabled" and set Port A Mode as "To BR Port A"
Board 2: Check Ethernet Enabled" and set Port A Mode as "To Port A"
Board 4: Check "Ethernet Enabled"
Board 5: Check "Ethernet Enabled"
No other programming is required. Once programed, all nodes can be accessed remotely through VeriFire Tools.
12
BroadR-Reach
X
B
A
RJ45
Additional
HS-NCM-W-2
X
Replacement
HS-NCM-W-2
A
B
RJ45
Existing
HS-NCM-W
Figure 12 Replacing a HS-NCM-W with a HS-NCM-W-2
A
RJ45
Additional
HS-NCM-W-2
A
B
VDSL
A
RJ45
Existing
Board 3
HS-NCM-W
HS-NCM Installation Document — P/N 54014:C1 12/15/2020
Board 4
X
B
Ethernet
To next node
Port B
X
B
Board 5