THIS DATA APPLIES TO 50GL UNITS WITH THE ICM INDOOR MOTOR FIOP
UNIT SIZE
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb)
COMPRESSOR
REFRIGERANT (R-410A)
Quantity (lb)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER COIL
Rows...Fins/in.
Face Area (sq. ft.)
CONDENSER FAN
Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)
EVAPORATOR COIL
Rows...Fins/in.
Face Area (sq. ft.)
EVAPORATOR BLOWER
Nominal Airflow (Cfm)
Size (in.)
Motor (HP)
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
LOSS-OF-CHARGE/LOW-PRESSURE SWITCH
(Liquid Line) (psig)
Cutout
Reset (Auto)
RETURN-AIR FILTERS (in.)
Throwaway
Table 7—ICM FIOP Physical Data—Unit 50GL
024
2
270
5.0
.057
1...17
10.9
2350
22
1/8 (825)
1/8 (825)
3...15
3.7
800
10x10
10x10
1/2
20 X 20 X 1
20 X 20 X 1
18
030
036
2-1/2
3
291
299
Scroll
5.5
6.9
AccuRater™ Piston
.057
.065
1...17
2...17
12.7
9.1
2350
2350
22
22
1/8 (825)
1/8 (825)
3...15
3...15
3.7
3.7
1000
1200
10x10
1/2
3/4
610 ± 15
420 ± 25
20 ± 5
45 ± 10
20 X 24 X 1
24 X 30 X 1
042
048
3-1/2
4
321
326
9.0
9.5
.070
.073
2...17
2...17
12.3
12.3
2350
3300
22
22
1/4 (1100)
1/4 (1100)
3...15
4...15
4.7
4.7
1400
1600
11x10
11x10
3/4
3/4
24 X 30 X 1
24 X 30 X 1
060
5
399
10.0
.086
2...17
16.4
3300
22
4...15
4.7
2000
11x10
1

Advertisement

Table of Contents
loading

Table of Contents