Fault Message
Total Power High ShtDwn
Volts L1-L2 High Shutdwn
Volts L1-L2 Low Shutdwn
Volts L2-L3 High Shutdwn
Volts L2-L3 Low Shutdwn
Volts L3-L1 High Shutdwn
Volts L3-L1 Low Shutdwn
* Programmable Interface Module (PIM) required
w Load management device (LCM, load shed kit, or RXT with combined interface/ load management board).
Applies during exercise runs and normal operation.
[
Figure 5-3 Fault Messages Displayed on the RDC2 Controller
66
Section 5 Troubleshooting
Action
SD
Measured load is greater than 102% of
the generator set power rating for more
than 1 minute. (38RCL only)
Shutdown
The controller shut down the generator
[
because the voltage measured from
Phase A to Phase B exceeded the high
limit for a time greater than the delay
setting 2 seconds.
Shutdown
The controller shut down the generator
[
because the voltage measured from
Phase A to Phase B was greater 5% of
rated, but less than the low voltage
setting for a time greater than the delay
setting 10 seconds.
Shutdown
The controller shut down the generator
[
because the voltage measured from
Phase B to Phase C exceeded the high
limit for a time greater than the delay
setting 2 seconds.
Shutdown
The controller shut down the generator
[
because the voltage measured from
Phase B to Phase C was greater 5% of
rated, but less than the low voltage
setting for a time greater than the delay
setting (default 10 seconds).
Shutdown
The controller shut down the generator
[
because the voltage measured from
Phase C to Phase A exceeded the high
limit for a time greater than the delay
setting. (default delay time is 2
seconds.)
Shutdown
The controller shut down the generator
[
because the voltage measured from
Phase C to Phase A was greater 5% of
rated, but less than the low voltage
setting for a time greater than the delay
setting.
Description/ Comments
Check
Reduce the load by
disconnecting non-essential
equipment. Check wiring and
troubleshoot connected
equipment.
Check for phase imbalance.
Check for very high power
factor loads.
Troubleshoot alternator; see
alternator service manual.
Troubleshoot alternator; see
alternator service manual.
Troubleshoot alternator; see
alternator service manual.
Troubleshoot alternator; see
alternator service manual.
Troubleshoot alternator; see
alternator service manual.
Troubleshoot alternator; see
alternator service manual.