Dimensions — Unit 38Ah104 - Carrier 38AH044-084 Installation, Start-Up And Service Instructions Manual

Air-cooled condensing units 50/60 hz
Table of Contents

Advertisement

Chart 1, Field Power Supply Connections
UNIT
VOLTAGE
Hz
DIAMETER — in. (mm)
38AH
208/230
60
460, 575,
104
60
380
346, 380/415
50
QUANTITY
3
5
(92)
2
8
3
5
(92)
1
8
3
5
(92)
1
8
Fig. 4 — Dimensions — Unit 38AH104
LEGEND
C
— Copper Fin Coils
MTG — Mounting
SAE — Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH-104---
5435 lb (2465 kg)
38AH-104--C
6160 lb (2794 kg)
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — 5 ft [1524 mm]
Sides — 6 ft [1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not
recommended for mounting unit to spring isolators.
4. Two 3
(92-mm) dia holes are recommended for parallel conductors on
5
8
208/230 v units.
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolators are used, a perimeter support channel between the unit
and the isolators is recommended.
7. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A
and 2B for A-D corner weights.
7