TROUBLESHOOTING E007 FAULT

WHAT IS AN E007 FAULT – An E007 fault is a dc-bus over-voltage fault.
Check the dynamic braking resistor circuit. Check that the resistor is connected to the correct terminals RB & P+. Check if the
resistor is open using a mul�meter.
If the decelera�on �me is too short, try increasing the decelera�on �me.
If the resistor ohm value might be the incorrect value and a new resistor with a lower ohm value may be required.
If a regenera�ve unit is used, then check that the regenera�ve unit is online and func�oning correctly and not in a fault
status. Also check if the regenera�ve is going offline due to power imbalance or noise.
If the status of the fault was while at STOP then this typically points to the input power spiking. Check the incoming power
for spikes or if large machinery is star�ng up causing sags and spikes. If this is the case, then try adding a line reactor in front
of the main power of the crane.
Contact Detroit Hoist for further assistance.

TROUBLESHOOTING E014 / E030 FAULT

WHAT IS AN E014 and E030 FAULT – An E014 and E030 fault are both referenced as ground faults.
Check the output conductors for short to ground. Try disconnec�ng the motor leads from the VFD side and see if the fault no
longer persists.
Test the motor with a megger for insula�on break down or for corona discharge insula�on damage.
Check the motor for high moisture contamina�on.
Contact Detroit Hoist for further assistance.