Compressor Motor With Circuit Breaker; Component Location - Carrier 06E Installation, Start-Up And Service Instructions Manual

Carrier compressors and condensing units installation, start-up and service instructions
Table of Contents

Advertisement

Table 1 — Electrical Data — Compressor Motor With Circuit Breaker
COMPRESSOR MOTOR DATA
Compressor
Voltage
Part Number
(3 Ph - 60 Hz) Hp
06E*
208/230
250
575
20
460
208/230
265
575
25
460
A
208/230
275
575
30
460
208/230
299
575
40
460
LEGEND
LRA — Locked Rotor Amps
MHA — Must Hold Amps
MTA — Must-Trip Amps
PW
— Part-Winding (Start)
RLA — Rated Load Amps
XL
— Across-the-Line (Start)
*Refer to physical data table to match compressor with correct com-
pressor or water-cooled condensing unit.
NOTES:
1. Compressor MTA and RLA values are maximum figures.
2. LRA values for PW second winding =
3. 3-Pole XL circuit breakers shown, other 3-Pole XL alternates
and 6-Pole PW breakers available. Terminal lugs for circuit
breakers available in package 06EA660152 (not shown).
LEGEND
C1
— Compressor Contactor
C2
— Compressor Contactor (PW)
CCB
— Compressor Circuit Breaker
CHR
— Crankcase Heater Relay
CR
— Control Relay
FU
— Fuse
GND
— Ground
HPS
— High-Pressure Switch
— Low-Pressure Switch
LPS
— National Electrical Code
NEC
NEMA — National Electrical
Manufacturer's Association
OPS
— Oil Pressure Switch
POR
— Pumpout Relay
TB
— Terminal Block
TDR
— Time Delay Relay
TM
— Timer Motor
TR
— Timer Relay
Maximum
Maximum
Must Trip
LRA-XL
RLA
Amps
108
87
345
45
36
120
54
44
173
140
112
446
57
46
164
70
56
223
168
135
506
65
52
176
84
68
253
236
189
690
94
75
276
118
95
345
1
/
the LRA – XL value.
2
Fig. 5 — Component Location
Motor
LRA-PW
Recommended
Winding
(first
Circuit Breaker
Resistance
winding)
Part No.
(Ohms)
207
0.32
HH83XB336
72
2.2
104
1.3
268
0.27
HH83XC509
98
1.6
134
1.1
304
0.22
HH83XC539
106
1.3
152
0.9
414
0.15
HH83XC537
165
1.0
207
0.58
4. Recommended RLA value shown is determined by: circuit
breaker must trip value ÷ 1.40. Use this recommended (and
minimum) RLA value to determine nameplate stamping, mini-
mum contactor sizing, and wire sizing. RECOMMENDED RLA
FOR 06E COMPRESSORS EQUALS: MUST-TRIP (MTA) OF
CARLYLE APPROVED OVERCURRENT DEVICE BEING
USED ÷ 1.40
5. Compressor operating amps at any specific condition can only
be determined from a performance curve.
6. Ohm values for resistance are approximate and shown for ref-
erence purposes only. Motors from different vendors and
motors of different efficiencies can differ up to 15% from data
shown.
7. Electrical data for compressor part numbers 06ER, 06EM and
50 Hz models (not shown) are available from Carrier Sales
Representative.
5
CIRCUIT BREAKER
Recommended
MHA MTA LRA
91
104
350
XA461
33
38
124
XA424
42
49
175
110
127 420
XA469
46
53
164
XA426
55
643
210
142
163 507
XA430
50
58
168
XA425
63
73
210
187
215 636
XA551
74
85
236
XA550
92
106
295
RLA
74.3
27.1
35.0
90.7
37.9
45.7
116.4
41.4
52.1
153.6
60.7
75.7