Refrigeration Cycle Diagram

• COOLING ONLY (LV-C362FLA0, LV-C422FLA0, LV-C482GLA0, LV-C602HLA0,
INDOOR UNIT
CAPILLARY TUBE
HEAT
EXCHANGER
(CONDENSER)
Pipe size(Diameter: ø)
MODEL
36K
42K
48K
60K
• Rated performance for refrigerant line length of: .7.5m
• If 36K Model is installed at a distance of 15m, 225g of refrigerant should be added (15-7.5)x30g=225g
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LV-C48BGLA0, LV-C60BHLA0)
LIQUID SIDE
GAS SIDE
Gas
Liquid
5/8"
3/8"
3/4"
3/8"
3/4"
1/2"
3/4"
1/2"
OUTDOOR UNIT
COMPRESSOR
Piping length(m)
Rated
Max.
7.5
15
7.5
15
7.5
15
7.5
15
- 9 -
HEAT
EXCHANGER
(CONDENSER)
*Additional
Elevation(m)
refrigerant
Rated
Max.
5
10
5
10
5
10
5
10
LGE Internal Use Only
(g/m)
30
35
40
45