Connection To Oil Supply Valve; Connection To Oil Return Valve - GE Kelman Minitrans Installation Manual

Transformer oil dissolved gas and moisture monitor
Hide thumbs Also See for Kelman Minitrans:
Table of Contents

Advertisement

Do not
Do not
is performed by GE-trained and certified personnel during the commissioning
phase to prevent air bubbles from entering the transformer.

8.3.3 Connection to oil supply valve

Oil is typically taken from a valve midway up on the transformer or from an active cooling
loop (see Section 8 for information on valve selection). Oil must be taken from a location
where the oil is well mixed and in the active flow of the transformer oil. The temperature
of the oil at this location should not exceed 100 °C or be lower than −10 °C.
distance from the oil return valve should be at least 30 cm (12 in.).
These points must be observed when connecting to the oil supply valve:
Locate the valve on the transformer chosen for the oil supply line. Identify the items
needed to adapt the oil supply valve to a ¼ in. female NPT fitting. Select fittings and
adaptors made from stainless steel, brass or black iron.
Do not
negatively affect the gas concentrations in the sample line.
All pipe fittings should be tight and all threaded pipe fittings tightly wrapped with
PTFE tape with a light coating of PTFE paste or other quality pipe thread sealant
applied over the taped male threads to prevent leaks. Both of these items are
included in the product installation kit.
or three wraps for large pipe fittings.

8.3.4 Connection to oil return valve

Oil is typically returned to a valve lower on the transformer — this can be the
transformer drain
30 cm (12 in.).
Do not
cooling loop.
The following points must be observed when connecting to the oil return valve (see
Section 8 for information on valve selection):
The return line to the transformer must be via the Return Assembly (see Figure 8-8 to
Figure 8-11). This assembly incorporates a check valve and port that facilitates
bleeding the system of air during the installation process. The bleed port must be
oriented up so that air can be drawn from the top. The assembly can be reconfigured
to fit the transformer valve and adaptor. This assembly must be adapted from a ¼ in.
female NPT fitting to the valve on the transformer.
MA-005 - Minitrans Installation Manual - Rev 4.5
use any type of thread sealant on compression-type tube fittings.
open the valves on the transformer or the stainless steel tubing. This
use galvanised steel, copper or plastic fittings as these materials can
valve. Note: The distance from the oil supply valve should be at least
return the oil into a high pressure area on the transformer, such as a
Note: GE recommends two wraps of PTFE tape
Note: The