Trane CSRA025FAF0 Installation Operation & Maintenance page 34

Table of Contents

Advertisement

34
Installation
Figure 15 — Typical Insulated, Spiralled Heat Tape Installation
Table 2A — Non-Insulated, Non-Thermostatically Controlled Heat Tape
with Outer Wrap
Application
Technique "Straight"
Heat Tape Req. per Linear
Ft. of Pipe
Protection Down to (°F)
"Spiralled"
Heat Tape Req. per Linear
Ft. of Pipe
Protection Down to (°F)
Note: Spiralled applications are twisted around pipe 3 turns per linear foot of
pipe.
Pipe Size
2"
2-1/2"
3"
12"
12"
12"
11°
15°
28"
31"
35"
-27°
-23°
-20°
4"
5"
12"
12"
20°
22°
47"
54"
-17°
-15°
CSRA-SVX02A-EN